Configuring an M1 CPU with Concept

Changing the Modbus Address

Overview

Each port can be assigned a Modbus network address in the range 1 ... 247. That

 

 

address must be unique with respect to all other device addresses on the same

 

 

Modbus networks.

 

 

Since Modbus port 1 and Modbus port 2 are always on different Modbus networks,

 

 

they can both be assigned the same address value without conflict. The factory-set

 

 

default for both ports is address 1.

Procedure

 

 

 

From the Modbus Port Settings dialog box, perform the steps in the following table

 

 

to change the Modbus Address:

 

 

 

 

 

 

 

Step

Address

 

 

 

 

 

 

 

 

1

Click on the Address field for the appropriate Modbus port.

 

 

 

 

 

 

 

 

2

Type a new value in the range 1 ... 247.

 

 

 

 

 

 

Set the Stop Bit at 1.

Bridge mode is not supported.

342

870 USE 101 10 V.2

Page 342
Image 342