I/O Mapping an I/OBus Network with Concept

Supporting an I/O Map for an I/OBus Network

Introduction

Three Processor Adapters have an I/OBus communication port that enables them

 

to control and communicate with other network slave I/O:

 

λ 171 CCS 760 00

 

λ 171 CCC 760 10

 

λ 171 CCC 960 20

 

λ 171 CCC 960 30

 

If you are using I/OBus to control network I/O, you need to write an I/O Map in your

 

configuration. This section describes the configuration parameters required to

 

support an I/O Map for I/OBus.

I/O Map

 

Be sure that you have reserved enough words for I/O mapping to support your I/O

Reserved Words

Bus network. The default setting is 144 words. To estimate the number of words

 

you require, allow:

λ16 words for overhead

λ10 words/module on the network (including both the local and the network I/O)

Allot sufficient memory to completely I/O Map your network, while preserving as much user memory as possible for your application program.

Number of

Be sure that the number of segments is set to 2. If you have changed this setting to

Segments

1, you will not be able to support an I/OBus network.

Next Step

 

Once you are sure that your Configuration Overview parameters are set properly,

 

you can access an I/O Map screen for an I/OBus network.

 

 

362

870 USE 101 10 V.2

Page 362
Image 362
Schneider Electric Processor Adapter manual Reserved Words, Segments