Configuring a Modbus Plus Network in Concept with Peer Cop

Devices on the Network

Introduction

This section describes the three CPUs which exchange data over the sample

 

 

Modbus Plus network and the strategy used to assign node addresses.

Devices

 

 

 

 

The three CPUs and their functions are described in the following table:

 

 

 

 

 

 

 

 

MB+ Address

CPU

Function

 

 

 

 

 

 

 

 

 

1

Pentium supervisory computer with an

Receives specific input data

 

 

 

 

ATRIUM 180-CCO-111-01 host-based

and sends global outputs

 

 

 

 

PLC card

 

 

 

 

 

 

 

 

 

 

2

171 CCS 760 00 Momentum M1

Controls I/OBus network

 

 

 

 

Processor Adapter with

and exchanges data with

 

 

 

 

172 PNN 210 22 Modbus Plus Option

ATRIUM supervisor

 

 

 

 

Adapter

 

 

 

 

 

 

 

 

 

 

3

171 CCS 760 00 Momentum M1

Controls I/OBus network

 

 

 

 

Processor Adapter with

and exchanges data with

 

 

 

 

172 PNN 210 22 Modbus Plus Option

ATRIUM supervisor

 

 

 

 

Adapter

 

 

 

 

 

 

 

 

Address

 

 

 

 

In this type of architecture, assign the lowest network address (1) to the

Strategy

supervisory computer. When the network initializes, the supervisor will be the first

 

 

device to get the token, and the token rotation table will be built with respect to the

 

 

supervising device.

 

 

 

 

 

 

 

 

388

870 USE 101 10 V.2

Page 388
Image 388
Schneider Electric Processor Adapter manual Devices on the Network