Overview of Momentum M1 Processor Adapters

171 CCS 760 00, Continued

 

 

Specifications,

 

 

 

 

 

 

I/O Servicing

 

 

Continued

 

 

 

 

 

Local I/O

Services all the points on any host Momentum I/O base

 

 

 

 

 

 

 

 

Watchdog timeout

419 ms

 

 

 

 

 

 

Logic solve time

0.25 ms/k ladder logic instructions

 

 

 

 

 

 

Mechanical

 

 

 

 

 

 

 

Weight

42.5 g (1.5 oz.)

 

 

 

 

 

 

Dimensions (HxDxW)

25.9x61.02x125mm

 

 

 

(1.01 x 2.37 x 4.86 in)

 

 

 

 

 

 

Material (Enclosures/

Lexan

 

 

bezels)

 

 

 

 

 

 

 

Operating Conditions

 

 

 

 

 

 

 

Temperature

0 ... 60 degrees C

 

 

 

 

 

 

Humidity

5 ... 95% (noncondensing)

 

 

 

 

 

 

Chemical interactions

Enclosures and bezels are made of Lexan,

 

 

 

a polycarbonate that can be damaged by strong

 

 

 

alkaline solutions

 

 

 

 

 

 

Altitude, full operation

2000m (6500ft)

 

 

 

 

 

 

Vibration

10 ... 57Hz @ 0.075mm displacement amplitude

 

 

 

57...150Hz @ 1g

 

 

 

Ref. IEC 68-2-6 FC

 

 

 

 

 

 

Shock

+/-15g peak, 11ms, half sine wave

 

 

 

Ref. IEC 68-2-27 EA

 

 

 

 

 

 

RFI Susceptibility/

Meets CE mark requirements for open equipment.

 

 

immunity

Open equipment should be installed in an industry-

 

 

 

standard enclosure, with access restricted to qualified

 

 

 

service personnel.

 

 

 

 

 

 

Storage Conditions

 

 

 

 

 

 

 

Temperature

-40 ... +85 degrees C

 

 

 

 

 

 

Humidity

5 ... 95% (noncondensing)

 

 

 

 

 

 

Safety Parameters

 

 

 

 

 

 

 

Degree of protection

Unintentional access (UL 508 Type 1, NEMA250 Type 1,

 

 

 

IP20 conforming to IEC529)

 

 

 

 

 

 

Di-electric strength

RS232 and I/OBus are non-isolated from logic common

 

 

 

 

 

 

Ground continuity

30 A test on the exposed metal connector

 

 

 

 

 

 

Agency Approvals

lUL 508, CSA, CUL, CE

 

 

 

FM class1, div2

 

 

 

 

 

870 USE 101 10 V.2

37

Page 37
Image 37
Schneider Electric Processor Adapter manual Temperature 40 ... +85 degrees C Humidity 95% noncondensing