Friedrich 920-159-01 (10-03) II. Installation, Utility Closet Dimensions, Typical Utility Closet

Models: 920-159-01 (10-03)

1 16
Download 16 pages 47.8 Kb
Page 5
Image 5
II. Installation

920-159-01 (10-03)

II. Installation

1) Utility Closet Dimensions

Recommended utility closet dimensions and a typical indoor installation are illustrated in Figure 1. Three inches minimum clearance on three sides of the unit must be allowed for return airflow, installation access and service access. See Figures 1 & 2 for clearances and reference dimensions.

Figure 3

Typical Utility Closet

Chassis Shown in Closet, on Optional Platform

Field-supplied

Rigid Ductwork

 

Filter (25" x 20")

 

58"

 

Exterior Wall

 

Flexible Ductwork

Power

VPAWP1-8/1-14 Wall Plenum

 

Disconnect

Plenum

 

29"

VPRG4 Access Panel &

Return Air Filter Grille

Optional Platform 1) Utility Closet Dimensions

3" Clearance on all

 

 

three sides

 

VPDP1 drain pan

minimum for

 

Chassis is

beneath unit is

 

 

shipped with

required on all

 

vibration

VEA/VHA24 units.

 

isolators

Drain pan must be

 

installed

installed prior to

 

 

chassis installation

Figure 4

Top View

control box

 

 

electrical

 

entrance

Vert-I-Pak Chassis 2-ton dimensions: 23" wide x 23" deep x 47 1/4" high.

VPAWP1-8/1-14 Wall Plenum cut-out dimensions 24 5/8" wide x 30 7/8" high.

VPRG4 Access Panel cutout dimensions: 27" wide by 55 3/4" high.

See Figure 8 (Page 10) for proper chassis installation.

NOTE: Drain pan must be installed in closet prior to chassis insertion into plenum. See Figure 7 (page 8) for drain pan installation details.

5

Page 5
Image 5
Friedrich 920-159-01 (10-03) operation manual II. Installation, Utility Closet Dimensions, Typical Utility Closet, Top View