Friedrich PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS manual Lintel Installation

Models: PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS

1 12
Download 12 pages 60.44 Kb
Page 5
Image 5
Typical Wall Sleeve Installation (PXWS)

Typical Wall Sleeve Installation (PXWS)

Lintel Used To Support Masonry Walls

42¼" Minimum

Electrical Receptacle

16¼"

50"Max Insulation

Maximum10"

Wall

Opening

 

 

13

¾"

 

Electrical

 

 

 

Receptacle

 

Main Studs

Lintel Installation

Jack

 

Smooth side of clip on Room side

Stud

LINTEL

MountingHoles

Screw

Note the use of a lintel under the first course of bricks above the wall sleeve. Do not use the wall sleeve as a lintel. The mounting screw holes shown are to be made by the installer.

No holes are permitted in the top or bottom of the sleeve. (Exception: PXDR10 Drain Kit)

Extended Wall Sleeve Installation and Sealant Locations (PXWE)

Wall Sleeve Extension, 42" X 16" Frame, 20 gauge minimum, painted or aluminum

Wall Sleeve

Outside Edge

Insulation

Air

Baffles

Width of Wall

 

 

 

Drip

 

 

Supplied)

Condensate

 

Panel

(Field

 

 

 

 

 

Four

Condensate

Notches

Sealant inside (4) bottom corners

IMPORTANT NOTE: The silicone bead MUST extend 3" up the side of the two flanges to prevent condensate from leaking.

5

Page 5
Image 5
Friedrich PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS Lintel Installation, Typical Wall Sleeve Installation PXWS