Typical Wall Sleeve Installation (PXWS)
Lintel Used To Support Masonry Walls
42¼" Minimum
Electrical Receptacle
16¼"
50"Max Insulation
Maximum10"
Wall | Opening |
|
| 13 | ¾" | |
| Electrical | ||
|
| ||
| Receptacle |
| |
Main Studs | Lintel Installation | ||
Jack | |||
| Smooth side of clip on Room side |
Stud
LINTEL
MountingHoles
Screw
Note the use of a lintel under the first course of bricks above the wall sleeve. Do not use the wall sleeve as a lintel. The mounting screw holes shown are to be made by the installer.
No holes are permitted in the top or bottom of the sleeve. (Exception: PXDR10 Drain Kit)
Extended Wall Sleeve Installation and Sealant Locations (PXWE)
Wall Sleeve Extension, 42" X 16" Frame, 20 gauge minimum, painted or aluminum
Wall Sleeve
Outside Edge
Insulation
Air
Baffles
Width of Wall
|
|
| Drip |
|
| Supplied) | |
Condensate |
| ||
Panel | (Field |
|
|
|
|
|
Four
Condensate
Notches
Sealant inside (4) bottom corners
IMPORTANT NOTE: The silicone bead MUST extend 3" up the side of the two flanges to prevent condensate from leaking.