WallMaster® PTAC/PTHP Engineering Specifications

All units shall be factory assembled, piped, wired and fully charged with R-22. All units shall be certified in accordance with ARI Standard 310 for air conditioners and ARI Standard 380 for heat pumps. Units shall be UL listed and carry a UL label. All units shall be factory run-tested to check operation and be Friedrich WallMaster® or equivalent.

The basic unit shall not exceed 16" high x 42" wide. Overall depth of the unit from the rear of the Friedrich wall sleeve to the front of the decorative front cover shall not exceed 21¼". The unit shall be designed so that room intrusion may be as little as 7¼". Installations in walls deeper than 13 ¼" may be accomplished with the use of a wall sleeve extension (PXWE). Unit shall draw in ambient air through both sides of an outdoor architectural louver or grille measuring 42" wide x 16" high and shall exhaust heated air out the middle portion of the louver. The architectural louver and wall sleeve shall be designed so that the louver may be installed from the inside of the building.

REFRIGERATION SYSTEM - The refrigeration system shall consist of a hermetically sealed rotary compressor that is externally mounted on vibration isolators no smaller than 1 ¾" dia. X 1 ½" high; condenser and evaporator coils constructed of copper tubes and aluminum plate fins; and capillaries as expansion devices. Unit shall have a fan slinger ring to increase efficiency and condensate disposal and have a drain pan capable of retaining 1½ gallons of condensate. A tertiary condensate removal system shall also be incorporated for back up and shall overflow through the wall sleeve and to the outside of the building as a safeguard against damage to the interior room.

AIR HANDLING SECTION - The evaporator and condenser fans shall be driven by a single, totally enclosed, ball bearing, permanently lubricated split capacitor, "clam-shell" style fan motor. Airflow shall be directed into the room by a single, injection molded, high-impact polystyrene discharge grille. The grill shall have openings no larger than 3/8" high x 3" wide to prevent personal injury or damage to the PTAC unit, and will be reversible to allow air to be directed upward or outward as determined by the installer.

The chassis shall have a built-in damper capable of providing at least 60 CFM of fresh air into the conditioned area. A fine mesh screen shall filter the incoming fresh air. There must be a provision for locking the damper closed to ensure a proper seal.

CONTROLS - Covered controls shall be accessible in a compartment at least 9" wide with the controls no deeper than 1¼" in the opening to facilitate easy operation of the unit. Controls shall include dual rotary knobs for setting of the thermostat and for mode control. The knobs will be tamper proof to prohibit the removal of knobs by the user and shall feature a temperature- limiting device adjustable by the owner. The control panel shall be clearly marked and easy to read. Universal symbols shall be used with markings no smaller than 12-point type. The chassis may be ordered with the option of remote thermostat control.

Other controls accessible without removal of the chassis shall include fan cycle switch, fresh air vent control and emergency heat override switch (heat pump only).

GENERAL CONSTRUCTION - The wall sleeve shall be constructed of 18 gauge G90 zinc-coated steel. It shall be prepared by a process where it is zinc phosphate pretreated and sealed with a chromate rinse, then powder coated for maximum coverage and protection. The sleeve shall be shipped with a protective weatherboard and a structural center support, and be insulated for thermal efficiency. The grille or louver shall be shipped separately and made from stamped or extruded anodized aluminum. All louvers shall be in the horizontal plane.

The front panel shall lock to the chassis by means of two factory-supplied thumbscrews to prevent tampering. The front panel will feature a contoured discharge with no sharp corners. The air filters shall be reusable and be accessible without removal of the front cover.

All 265V units shall possess an integral, over-current time-delay protective device.

The unit shall have a plastic fan, fan shroud and drain pan for corrosion protection and to help prevent rust on the side of the building below the outdoor louver.

A complete line of accessories shall be available from Friedrich to equip the PTAC for a multitude of applications.

Friedrich Installation/Start-Up Specialists shall be available to answer questions regarding proper installation practices and in some cases for on-site start-up inspections.

7

Page 7
Image 7
Friedrich PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS manual WallMaster PTAC/PTHP Engineering Specifications

PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS specifications

Friedrich Packaged Terminal Air Conditioners (PTACs) and Heat Pumps represent a cutting-edge solution for climate control in a variety of settings, especially in hotels, apartments, and commercial spaces. These units are designed to provide individual room temperature management, offering both heating and cooling options to ensure comfort year-round.

One of the standout features of Friedrich PTACs is their energy efficiency. These units often meet or exceed ENERGY STAR certification, which signifies superior efficiency compared to traditional models. This efficiency translates to lower energy bills and a reduced environmental footprint, making them a sustainable choice for modern building owners.

Friedrich utilizes advanced technologies in their PTAC units to enhance performance and reliability. This includes features like variable-speed compressors that adjust cooling and heating output based on real-time room demands, leading to more consistent temperatures and improved energy savings. Additionally, some units come equipped with digital controls and remote management capabilities, allowing users to easily monitor and adjust settings from a distance.

Another key characteristic of Friedrich PTACs is their quiet operation. By incorporating sound-reducing technologies and design features, these units minimize operational noise, creating a more pleasant environment for occupants. This is particularly important in settings like hotels and hospitals, where peace and quiet are paramount.

Friedrich's commitment to durability is evident in their robust construction. The units are built with high-quality materials designed to withstand the rigors of constant use, ensuring longevity. The design also includes easily accessible components for convenient maintenance and servicing, which helps to further extend the life of the unit.

Moreover, Friedrich offers a variety of models tailored to diverse installation needs. With options for different capacities, styles, and aesthetic finishes, building owners can find the perfect match for their spaces without sacrificing performance.

In conclusion, Friedrich Packaged Terminal Air Conditioners and Heat Pumps are an excellent choice for anyone looking to enhance indoor climate control. With their energy efficiency, advanced technologies, quiet operation, and durable construction, they set a high standard in the HVAC industry, ensuring comfort for occupants while also addressing the growing demand for environmentally sustainable solutions.