WallMaster® PTAC/PTHP Engineering Specifications
All units shall be factory assembled, piped, wired and fully charged with
The basic unit shall not exceed 16" high x 42" wide. Overall depth of the unit from the rear of the Friedrich wall sleeve to the front of the decorative front cover shall not exceed 21¼". The unit shall be designed so that room intrusion may be as little as 7¼". Installations in walls deeper than 13 ¼" may be accomplished with the use of a wall sleeve extension (PXWE). Unit shall draw in ambient air through both sides of an outdoor architectural louver or grille measuring 42" wide x 16" high and shall exhaust heated air out the middle portion of the louver. The architectural louver and wall sleeve shall be designed so that the louver may be installed from the inside of the building.
REFRIGERATION SYSTEM - The refrigeration system shall consist of a hermetically sealed rotary compressor that is externally mounted on vibration isolators no smaller than 1 ¾" dia. X 1 ½" high; condenser and evaporator coils constructed of copper tubes and aluminum plate fins; and capillaries as expansion devices. Unit shall have a fan slinger ring to increase efficiency and condensate disposal and have a drain pan capable of retaining 1½ gallons of condensate. A tertiary condensate removal system shall also be incorporated for back up and shall overflow through the wall sleeve and to the outside of the building as a safeguard against damage to the interior room.
AIR HANDLING SECTION - The evaporator and condenser fans shall be driven by a single, totally enclosed, ball bearing, permanently lubricated split capacitor,
The chassis shall have a
CONTROLS - Covered controls shall be accessible in a compartment at least 9" wide with the controls no deeper than 1¼" in the opening to facilitate easy operation of the unit. Controls shall include dual rotary knobs for setting of the thermostat and for mode control. The knobs will be tamper proof to prohibit the removal of knobs by the user and shall feature a temperature- limiting device adjustable by the owner. The control panel shall be clearly marked and easy to read. Universal symbols shall be used with markings no smaller than
Other controls accessible without removal of the chassis shall include fan cycle switch, fresh air vent control and emergency heat override switch (heat pump only).
GENERAL CONSTRUCTION - The wall sleeve shall be constructed of 18 gauge G90
The front panel shall lock to the chassis by means of two
All 265V units shall possess an integral,
The unit shall have a plastic fan, fan shroud and drain pan for corrosion protection and to help prevent rust on the side of the building below the outdoor louver.
A complete line of accessories shall be available from Friedrich to equip the PTAC for a multitude of applications.