1.2.4Power Specifications

Two power input modes are available; single-phase power feed and three-phase power input.

The following table lists power conditions for the single-phase power feed.

TABLE 1-4Power Specifications

 

 

 

M9000

 

 

 

 

 

Base cabinet + expansion

Item

 

M8000

Base cabinet only

cabinet

 

 

 

 

 

Input power:

Voltage [V]

AC200 to 240 ±10%

 

 

Single-phase

Frequency [Hz]

50/60 (+2% / -4%)

 

 

power input

 

 

 

 

 

 

Power consumption [kW]

10.5 1

21.3 2

42.6 3

Apparent power [kW]

11.0 1

22.4 2

44.8 3

Power

Power Input

3.0

 

 

conditions

cable [m]

 

 

 

 

Plug shape

Japan: 30 A-250 V, 4P hook lock (The wiring between X and Y must be

 

 

single-phase 200-VAC wiring.)

 

 

 

North America: NEMA L6-30P

 

 

 

Europe: EN60309 (32A)

 

 

Number of plugs

3 (single power

5 (single power feed)

10 (single power feed)

 

 

feed)

10 (dual power feed)

20 (dual power feed)

 

 

6 (dual power

 

 

 

 

feed)

 

 

 

 

 

 

 

1This value applies if 4 CPU/Memory Board Units and 4 I/O units are mounted.

2This value applies if 8 CPU/Memory Board Units and 8 I/O units are mounted.

3This value applies if 16 CPU/Memory Board Units and 16 I/O units are mounted.

To use a three-phase power source, a three-phase power feed option and a power supply cabinet for mounting the option are required. The three-phase power feed has two connection options: a star connection that connects a neutral line and each phase, and a delta connection that connects each phase.

For details on specifications for the three-phase power feed, see the SPARC Enterprise M8000/M9000 Servers Site Planning Guide.

Chapter 1 System Overview 1-11