Remote Thermostat Control

Heat Pump Models

The Zoneline® 3800 and 5800 Series heat pump units may be connected to a single-stage cooling/two-stage heating thermostat designed for use with heat pump systems. GE offers 3 thermostats compatible with the 3800 and 5800 series units:

RAK147 —

RAK148D1 —

RAK148P1 —

mechanical

solid-state digital

solid-state digital

manual

manual

programmable

changeover

changeover

auto-changeover

thermostat

thermostat

thermostat

requiring 6

requiring 6

requiring 6

connection wires.

connection wires.

connection wires.

Please see page 57 for installation recommendations for the remote thermostat wiring. Compatibility of other thermostats considered for use with the GE Zoneline® is the responsibility of the customer.

The control voltage on the remote control conductors is 24 VAC.

The Class 2 Mode Switch, dip switch #4 on the auxiliary control board on both the 3800 series and the 5800 series, must be set to the ON/UP mode to enable remote thermostat control. Refer to installation instructions packaged with the chassis.

The fan speed for the 3800 and 5800 series in remote thermostat operation is selected by the connection of the fan wire from the thermostat to either the HIGH or LOW terminal on the unit. See the sketch of the unit terminals for the location of the HIGH and LOW fan speed terminals. Operating the unit in low fan speed reduces the operating sound level of the unit.

When connected to a remote thermostat, the indoor air temperature sensing is shifted from the unit to the remote thermostat. For this reason, the units will operate slightly differently when connected to a remote thermostat. The following chart shows the unit operation when connected to a remote thermostat.

Temperature Boost option should not be used with remote thermostat operation since this will cause the unit to switch to resistance heat when outdoor temperatures are below 46ºF.

Feature

Heat Pump

Electric Heat

Indoor Frost Control

Yes

Yes

Freeze Sentinel

Yes

Yes

Auto Fan Speed

No

No

Electronic

 

 

Temperature Limiting

No

No

Switch to Resistance

 

 

Heat Based On Indoor

Determined by

 

Temperature

Remote Thermostat

N/A

Switch to Resistance

 

 

Heat Based On

 

 

Outdoor Temperature

Yes

N/A

Reverse Cycle Defrost

Yes

N/A

Simultaneous

 

 

Resistance Heat

 

 

with Heat Pump

No

N/A

Resistance Heat

 

 

Lockout

Yes

N/A

“Smart Fan”

Fan ON/AUTO Set On

Fan ON/AUTO Set On

Fan Cycle

Remote Thermostat

Remote Thermostat

Central Desk Control

Yes

Yes

Field Wiring Terminal

R

— 24V AC

GL

Low-Speed Fan

GH — High-Speed Fan

B

— Reversing Valve

Y

— Compressor

W

— Heater

C

— Common - Ground

 

 

R GL GH

B Y W C

 

 

 

 

 

 

 

 

 

 

Common — Ground

 

 

 

 

 

 

 

 

 

 

White — Heater

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yellow — Compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Black — Reversing Valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Green — High-Speed Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Green — Low-Speed Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Red — 24V AC

 

 

 

 

 

 

 

 

 

 

Remote Thermostat Control Selection Chart For Zoneline Packaged Terminal Units

Zoneline Series

Thermostat Model

Type

Function

Low-Voltage Conductors

 

 

 

 

 

2800

RAK163A1

Mechanical

 

4

 

 

 

Cooling and Heating

 

 

RAK164D1

Digital

5

 

 

 

 

 

 

RAK164P1

Digital Programmable

 

5

 

 

 

 

 

 

 

 

 

 

3800 and 5800

RAK147

Mechanical

Single Stage Cooling –

6

 

 

 

 

 

RAK148D1

Digital

6

 

2 Stage Heating

 

 

 

 

 

RAK148P1

Digital Programmable

6

 

 

 

 

 

 

 

Thermostat wire size – up to 60 feet AWG20 – up to 66 feet AWG18