Safety Instructions

Operating Instructions

Auxiliary controls on your Zoneline.

External Fan (Obtained locally)

When connected, an auxiliary or external fan can be controlled with the indoor fan motor on the Zoneline. Connections provide 24 V AC to energize a remote relay, turning on the external fan.

External Fan

Central Desk Control

When connected, the unit can be turned ON or OFF with a switch located at the Central Control Panel. A separate wire pair must be run from each separate controlling switch to each individual Zoneline.

Central Desk Control

Care and Cleaning

Troubleshooting Tips

Consumer Support

Remote Thermostat

When connected, the unit will be controlled by a remote thermostat.

NOTE: The number 4 dip switch must be in the enabled (UP) position to activate the remote thermostat. (See the installation instructions supplied with the remote thermostat.)

IMPORTANT:

The Zoneline thermostat connections provide 24 V AC only.

If using a digital/electronic wall thermostat, you must set it to the 24 V AC setting.

See the Installation Instructions for the wall thermostat.

Red - 24 V AC only

Green - Low Speed Fan

Green - High Speed Fan

Black - Solenoid

Yellow - Compressor

White - Heater

Common - Ground

CAUTION:

Damage to a wall thermostat or to the Zoneline electronics can result from improper connections. Special care must be used in connecting the wires. No line voltage connections should be made to any circuit. Isolate all wires in building from line voltage.

8

Page 8
Image 8
GE 2900, TINSEA530JBRZ, 3900 installation instructions External Fan Obtained locally, Central Desk Control