Image 6
Battery and Holder

Installation (cont’d)

MX60 Controller DANGER Manual background

HAZARDOUS VOLTAGE

(Can Cause Severe Injury or Death)

Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.

ATTENTION!

This applies only to the switches with the RM4-CAT exerciser option:

Only after ATS installation, connect a commercial-grade alkaline 9V battery to the MX60 controller via the har- ness connected to the controller. The battery should be placed in the holder installed just above the controller.

The battery is used to maintain the exerciser function in the event of power outage. The battery should be replaced at least once a year. If the battery is not

Battery and Holder

Battery Harness

MX60 Controller

(Under Cover)

installed and/or replaced as recommended, an exerciser set from the front panel will lose its settings during power outages and the exerciser will not work.

Note: Battery life if reduced if neither source is avail- able. Typical battery life when both sources are unavailable is 21 days.

Should the battery connection become disconnected in shipping, take the controller cover off and plug the harness into the receptacle in the top right corner of the MX controller as shown in figure 2 and 5. Reinstall the cover and connect the battery.