GE ZTX manual Installation cont’d, Power Connections, Danger, Hazardous Voltage, Switch Size

Models: ZTX

1 18
Download 18 pages 45.06 Kb
Page 4
Image 4
Installation (cont’d)

Installation (cont’d)

Power Connections DANGER Switch Size

HAZARDOUS VOLTAGE

(Can Cause Severe Injury or Death)

Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.

Power Connections

GE Zenith transfer switches are supplied with UL listed solderless screw type terminals as standard for the Normal, Emergency and Load power connections.

Table 1 lists the number and sizes of cable lugs supplied as standard for each switch amp rating.

Connect the Normal, Emergency, and Load conductors to the clearly marked terminals on the transfer switch. Remove surface oxides from cables by cleaning with a wire brush. Verify that all connections are correct before tightening the lugs. All cable lug connections must be tightened to the proper torque values as shown in Table 2.

NOTE: Do not run cables or wiring behind front-connected transfer switches.

Screw Type Terminals for External Power Connections

Switch Size

Utility, Generator and Load Terminals

Fully Rated Neutral Bar (When Required)

(Amps)

 

 

 

 

Cable Per Pole

Range of Wire Sizes

No. of Cables

Range of Wire Sizes

 

40

1

#8 to 3/0 AWG

3

#8 to 1/0 AWG

80

1

#8 to 3/0 AWG

3

#8 to 1/0 AWG

100

1

#8 to 3/0 AWG

3

#8 to 1/0 AWG

150

1

#8 to 3/0 AWG

3

#8 AWG to 300 MCM

200, 225, 250*

1

#6 AWG to 250 MCM

3

#6 AWG to 300 MCM

300, 400

1

#4 AWG to 600 MCM

3

#4 AWG to 300 MCM

Table 1

* IEC Rating Only

UTILITY

LOAD

TERMINALS

T1 T2 T3

Tip!

TERMINALS

N1 N2 N3

 

BR

SWITCH

N

POSITION

INDICATOR

 

E1 E2 E3

GENERATOR

TERMINALS

T = Load N = Utility E = Generator

Figure 1 - Power Panel

OPTIONAL A4 CONTACT

OPERATES WHEN IN UTILITY POSITION

JP

OPTIONAL A3 CONTACT

OPERATES WHEN IN GENERATOR POSITION

Install

load

cables

first.

2

ZTX Operation and Maintenance Manual (72R-1000)

GE Zenith Controls

Page 4
Image 4
GE ZTX Installation cont’d, Power Connections, Danger, Hazardous Voltage, Can Cause Severe Injury or Death, Switch Size