GE ZTX Troubleshooting, Danger, Hazardous Voltage, Can Cause Severe Injury or Death, Symptom

Models: ZTX

1 18
Download 18 pages 45.06 Kb
Page 17
Image 17
Troubleshooting

Troubleshooting

Service must be performed by qualified personnel. DANGER Symptom

HAZARDOUS VOLTAGE

(Can Cause Severe Injury or Death)

Turn OFF all power before installation, adjustment, or removal of transfer switch or any of its components.

Service must be performed by qualified personnel.

Symptom

Possible Cause
Corrective Action

S1 or S2 Available LED not lit

Sources either fully or partially unacceptable

Check for under voltage

 

S1 or S2 breakers open

Check for missing phase (s)

 

 

Check for under frequency

 

 

 

ATS will not retransfer Load

T - Timer has not expired

 

back to Utility

Automatic Exerciser is in process

 

 

S1 Utility fully or partially unacceptable

 

 

 

 

ATS does not transfer Load to S2

S2 Generator fully or partially unacceptable

Set motor-saver to dropout below

(generator)

Motor loads on system creating enough back-

ATS Fail setpoint

 

EMF to keep missing phase from falling below

 

 

Fail setpoint.

 

 

 

 

S2 Generator will not start

X1 or X2 not connected

Check Generator Start wiring

 

 

 

S2 Generator will not shut down

U - Timer not expired

Wait for U timer to expire

 

Automatic Exerciser in process

 

 

 

 

All LEDs off

Keypad connector unplugged at Controller

 

 

Both source breakers open

 

 

 

 

ATS will not transfer in-phase

In-Phase monitor not on

Turn on In-Phase monitor

 

Frequency difference between S1 and

Adjust Generator governor to hold

 

S2 greater than 2Hz.

freqency closer to Utility

 

 

 

ATS will not retain a

Battery dead or missing

Replace battery with a fresh industrial

Set Automatic Exerciser

 

grade Alkaline battery

 

 

 

Timer/In-Phase LED constantly on

Both sources locked in frequency or one

Turn In-Phase monitor off

 

source greater than 20° out of phase

 

 

 

 

S1 and S2 LEDs Blinking

Phase Rotation Mis-match between sources

Rewire sources to be same rotation

 

 

 

S1 Position LED Blinking

SN limit switch bad or intermittent

Check connection or SN limit switch

 

 

 

S2 Position LED Blinking

SE Limit switch bad or intermittent

Check connection or SE limit switch

 

 

 

Both S1 and S2 Positioin

Solenoid bad or disconnected

Requires CANCEL key to clear -

LEDs Blinking

ATS contactor in mid-position

check Solenoid

 

 

Requires CANCEL key to clear -

 

 

Check both limit switches

 

 

 

 

 

Table 9

GE Zenith Controls

ZTX Operation and Maintenance Manual (72R-1000)

15

Page 17
Image 17
GE ZTX manual Troubleshooting, Danger, Hazardous Voltage, Can Cause Severe Injury or Death, Symptom, Possible Cause