Technical information

Technical characteristics

Table of Gemini switchboards’ technical characteristics

Size

 

1

2

3

4

5

6

 

Gemini with transparent door

 

1SL0211A00

1SL0212A00

1SL0213A00

1SL0214A00

1SL0215A00

1SL0216A00

 

Gemini with opaque door

 

1SL0201A00

1SL0202A00

1SL0203A00

1SL0204A00

1SL0205A00

1SL0206A00

 

External dimensions WxHxD (mm) 335x400x210

460x550x260

460x700x260

590x700x260

590x855x360

840x1005x360

 

Internal dimensions WxHxD (mm)

250x300x180

375x450x230

375x600x230

500x600x230

500x750x330

750x900x330

 

IP degree

 

IP66

IP66

IP66

IP66

IP66

IP66

 

Double isolation

 

Yes

Yes

Yes

Yes

Yes

Yes

 

IK degree

 

10

10

10

10

10

10

 

GWT (°C)

 

750

750

750

750

750

750

 

Operating temperature

-25 °C +100 °C

-25 °C +100 °C

-25 °C +100 °C

-25 °C +100 °C

-25 °C +100 °C

-25 °C +100 °C

 

No. of DIN modules

 

24 (12x2)

54 (18x3)

72 (18x4)

96 (24x4)

120 (24x5)

216 (36x6)

3

No. of vertical modules (H=150 mm)

2

3

4

4

5

6

Material

Thermoplastic

Thermoplastic

Thermoplastic

Thermoplastic

Thermoplastic

Thermoplastic

Color

Grey RAL7035

Grey RAL7035

Grey RAL7035

Grey RAL7035

Grey RAL7035

Grey RAL7035

 

Fast wiring system

 

Unifix L

Unifix L

Unifix L

Unifix L

Unifix L

Unifix L

 

No. of locks

 

2

2

2

2

3

3

 

Rated current In

 

400 A

400 A

400 A

400 A

400 A

400 A

 

Rated frequency

 

50-60 Hz

50-60 Hz

50-60 Hz

50-60 Hz

50-60 Hz

50-60 Hz

 

Maximum dissipation power (1)

 

45 W

72 W

85 W

102 W

156 W

248 W

 

STANDARD CEI EN 60439-1

 

 

 

 

 

 

 

 

Over-temperature (par. 8.2.1) (2)

 

 

 

 

 

 

 

 

 

- Max. dispersible power with

 

 

 

 

 

 

 

 

 

over-temperature of 25 °C

 

40 W

65 W

77 W

91 W

133 W

205 W

 

 

 

 

 

 

 

 

 

 

 

 

- Max. dispersible power with

 

 

 

 

 

 

 

 

 

over-temperature of 30 °C

 

45 W

72 W

85 W

102 W

156 W

248 W

 

 

 

 

 

 

 

 

 

 

 

 

- Max. dispersible power with

 

 

 

 

 

 

 

 

 

over-temperature of 35 °C

 

52 W

85 W

100 W

121 W

187 W

299 W

 

 

 

 

 

 

 

 

 

 

 

 

- Max. dispersible power with

 

 

 

 

 

 

 

 

 

over-temperature of 40 °C

 

62 W

100 W

118 W

143 W

221 W

355 W

 

 

 

 

 

 

 

 

 

 

Impulse withstand (par. 8.2.2)

 

 

 

 

 

 

 

 

 

- Rated service voltage

 

690 V

690 V

690 V

690 V

690 V

690 V

 

 

 

 

 

 

 

 

 

 

 

 

- Rated insulation voltage

 

800 V

800 V

800 V

800 V

800 V

800 V

 

 

 

 

 

 

 

 

 

 

 

- Rated impulse withstand voltage

8 kV

8 kV

8 kV

8 kV

8 kV

8 kV

 

 

 

 

 

 

 

 

 

 

Short circuit withstand (par. 8.2.3)

 

 

 

 

 

 

 

 

 

- Rated peak short-circuit current

 

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

(1)Maximum dissipation power data was obtained following the indications of Standard CEI 23-49, with a temperature difference of Dt=30 °C.

(2)Note to paragraph 8.2.1 of Standard CEI EN 60439-1

The table gives the thermal dissipation values of Gemini switchboards when they are wall-mounted. The dispersible power figures (in Watts) vary according to the overtemperature allowed in the accessible parts of the switchboard and must be compared with the total amount of power dissipated by all the components installed inside the switchboard taking into due account the factor of contemporaneity.

ABB

25

Page 25
Image 25
Gemini Industries 1SLC805002F0001 manual Technical information, Technical characteristics