Section 7 – Post Installation

QUIETPACT 55, 65, and 75 Recreational Vehicle Generators

7.4TESTING UNDER LOAD

Apply electrical loads equal to about 75 to 100 per- cent of the unit's rated wattage/amperage capacity.

Let the unit run at least 30 minutes with load applied. During this part of the test, check that the unit is not running excessively hot and that adequate cooling airflow is available. You must not allow the unit to overheat during prolonged operation.

NOTE:

OPTIONAL LP GAS FUEL SYSTEM

Fuel system is properly installed and checked for leaks.

Pressure at regulator inlet is correct.

Rated flow of primary regulator is correct.

All parts are properly installed.

Fuel system is properly tested/adjusted.

The generator engine is equipped with a high tem- perature switch. The switch has normally open (N.O.) contacts. When the engine temperature is too high, switch contacts close, and the engine shuts down automatically.

GENERAC RECOMMENDS THAT YOU TEST THE GENERATOR FOR ADEQUATE COOLING.

7.5INSTALLATION CHECKLIST

LOCATION AND SUPPORT

Generator is properly located.

Generator is properly supported.

Generator is properly restrained.

EXHAUST SYSTEM

Exhaust system complies with all applicable codes.

Exhaust system is properly and safely installed.

ELECTRICAL CONNECTIONS

Connections comply with local code requirements and all National Electrical Codes.

Junction box is properly installed.

Wiring meets all standards.

All connections are correct.

Conduit is properly installed and sealed.

Generator is properly bonded to the vehicle.

GENERATOR COMPARTMENT

 

BATTERY INSTALLATION

Compartment construction is proper.

 

Recommended battery is installed.

Holes/Openings are vapor-sealed.

 

Recommended cables are installed.

Compartment size is correct.

 

Cables are clean and tight.

Compartment is vapor-sealed.

 

Cables are connected properly.

Sound insulation is correct.

 

Proper ventilation is provided.

Floor cutouts are properly completed.

 

Terminals are coated with anti-corrosion grease,

 

 

and terminal covers are positioned.

COOLING AND VENTILATING AIR

Airflow is adequate.

Air inlet opening is correct.

Compensate for restrictions.

Check that installation has been tested.

GASOLINE FUEL SYSTEM

Fuel tank complies with all applicable codes.

Fuel system is properly installed and checked for leaks.

OPTIONAL ACCESSORIES

Check that remote start/stop panels (if used) are installed properly.

Check that hourmeter kit (if used) is installed properly.

Check that any other options and accessories (if used) are installed properly.

POST INSTALLATION TESTS

Check that all tests are completed properly.

DATE OF INSTALLATION ____________________________________________________

NAME OF INSTALLER ______________________________________________________

SIGNATURE OF INSTALLER ________________________________________________

Generac® Power Systems, Inc. 35

Page 37
Image 37
Generac 004702-0, 004703-0, 004704-0, 004705-0, 004706-0, 004707-0 owner manual Testing Under Load, Installation Checklist

004702-0, 004703-0, 004704-0, 004705-0, 004706-0, 004707-0 specifications

Generac has established itself as a leader in the power generation industry, particularly noted for its wide range of generators designed to provide reliable backup power. Among its various models, the Generac series consisting of the 004702-0, 004703-0, 004704-0, 004705-0, 004706-0, and 004707-0 stands out due to their dependable performance and innovative features. Each model in this series is engineered for both residential and light commercial applications, offering peace of mind during power outages.

One of the main features of these models is their state-of-the-art engine technology. Equipped with a Generac engine, these generators are designed to provide efficient, powerful performance. The engines are robust and designed to withstand extended use, ensuring that users can rely on them when needed most.

A standout feature is their Automatic Transfer Switch (ATS) capability. When the power goes out, these generators automatically switch on, providing uninterrupted power to essential appliances and systems in the home. This seamless transition is vital for maintaining safety and comfort during outages, eliminating the need for manual intervention.

Fuel efficiency is another area where these models excel. They utilize either natural gas or propane, offering flexibility in fuel choice depending on availability and preference. Their engineering is optimized for minimal fuel consumption while maximizing output, making them a cost-effective solution for power needs.

Furthermore, these models incorporate advanced monitoring and control systems. Users can conveniently monitor generator performance and status through an intuitive mobile app or control panel. This technology allows users to receive alerts and updates, ensuring they are always informed about the power situation at their location.

Noise reduction technology is also a key characteristic of this series. Generac's engineers have focused on minimizing sound output, providing a quieter operation compared to many other generators in the market. This feature is particularly beneficial for residential areas where noise can be a significant concern.

Overall, the Generac 004702-0, 004703-0, 004704-0, 004705-0, 004706-0, and 004707-0 models exemplify reliability, efficiency, and advanced engineering. Their comprehensive features and user-friendly technology make them an excellent choice for anyone seeking a dependable backup power solution.