Section 6 – Installation

QUIETPACT 55, 65, and 75 Recreational Vehicle Generators

The greater the airflow through the carburetor ven- turi, the lower the pressure at the venturi throat. The lower the pressure at the venturi throat, the greater the diaphragm movement, and the greater the move- ment of the regulator valve. The more the regulator valve opens, the greater the gas flow that is propor- tional to airflow through the generator.

The following facts about the secondary regulator must be emphasized:

The regulator must be sensitive to venturi throat pressure changes throughout the operating range.

The regulator must be properly adjusted so it will stop the flow of gas when the engine is not running (no air flow through the carburetor).

The slightest airflow (and vacuum in the venturi throat) should move the regulator valve off its seat and permit gas to flow.

6.5.7 FUEL SUPPLY LINES

LP gas lines must be accessible, but protected against possible damage.

Do NOT connect electrical wiring to any LP gas fuel line or run wiring alongside the lines.

Route gas lines away from hot engine exhausts.

Retain gas lines with metal clamps that do not have sharp edges.

Install an approved length of flexible hose between the gaseous fuel solenoid valve and rigid fuel sup- ply lines. The flexible line must be nonmetallic, nonorganic and nonconductive. It must be approved for use with LP gas.

DANGER

Gaseous fuel lines between the tank and the secondary regulator are under a positive pres- sure (about 11 inches water column). Gas pres- sure at the outlet side of the secondary regula- tor, however, is a negative pressure and can draw flame inside a line or fitting and cause an explosion.

6.5.9 LEAKAGE TESTS

Do not place the generator into service until you have properly tested the gas system for leaks. To test the system, you need a separate source of 12 volts DC to open the gaseous fuel solenoid valve.

The leak test must comply fully with NFPA, Paragraph 318. All connections, hoses, valve regula- tors, fittings, and other fuel system parts must be tested under gas or air pressure of not less than 90 psi (620 kPa), while using soap and water or an equivalent solution to check for leaks. Other approved methods of testing for leaks may be used, if appropriate. DO NOT USE ANY FLAME TO TEST FOR LEAKS.

6.6EXHAUST SYSTEM

The generator exhaust system must be safely and properly installed. Only approved mufflers and other exhaust system parts must be used. A properly installed exhaust system must be vapor tight, quiet and completely safe.

DANGER

The generator engine gives off DEADLY carbon

!monoxide gas through its exhaust system. This dangerous gas, if breathed in sufficient concen- trations, can cause unconsciousness or even death. Never operate the generator set with the vehicle inside any garage or other enclosed area. DO NOT OPERATE THE GENERATOR IF THE EXHAUST SYSTEM IS LEAKING OR HAS BEEN DAMAGED. SYMPTOMS OF CARBON MONOX- IDE POISONING ARE (a) inability to think coher- ently; (b) vomiting; (c) twitching muscles; (d) throbbing temples; (e) dizziness; (f) headaches;

(g) weakness; and (h) sleepiness. IF YOU FEEL ANY OF THESE SYMPTOMS, MOVE INTO FRESH AIR IMMEDIATELY. IF SYMPTOMS PERSIST, GET MEDICAL HELP. Do not operate the generator until its exhaust system has been inspected and properly repaired.

6.5.8 EXCESS FLOW VALVE

LP gas tanks should have an excess flow valve, according to NFPA 501C, Paragraph 3-4.4. This valve and the gas lines must be carefully sized so the valve will close when a fuel line is severed or broken. Consult the Natural-LP Gas Association for informa- tion and limitations of excess flow valves.

Manual shutoff valves on the supply tank and else- where in the system must be fully open when operat- ing the generator. The excess flow valve functions properly only if all valves are fully open.

Never tee the generator engine exhaust pipe

!into the vehicle engine exhaust piping. This causes excessive back pressure on the genera- tor engine. Also, water from one engine can damage the other engine.

Generac® Power Systems, Inc. 29

Page 31
Image 31
Generac 004702-0, 004703-0, 004704-0, 004705-0, 004706-0, 004707-0 Exhaust System, Fuel Supply Lines, Leakage Tests

004702-0, 004703-0, 004704-0, 004705-0, 004706-0, 004707-0 specifications

Generac has established itself as a leader in the power generation industry, particularly noted for its wide range of generators designed to provide reliable backup power. Among its various models, the Generac series consisting of the 004702-0, 004703-0, 004704-0, 004705-0, 004706-0, and 004707-0 stands out due to their dependable performance and innovative features. Each model in this series is engineered for both residential and light commercial applications, offering peace of mind during power outages.

One of the main features of these models is their state-of-the-art engine technology. Equipped with a Generac engine, these generators are designed to provide efficient, powerful performance. The engines are robust and designed to withstand extended use, ensuring that users can rely on them when needed most.

A standout feature is their Automatic Transfer Switch (ATS) capability. When the power goes out, these generators automatically switch on, providing uninterrupted power to essential appliances and systems in the home. This seamless transition is vital for maintaining safety and comfort during outages, eliminating the need for manual intervention.

Fuel efficiency is another area where these models excel. They utilize either natural gas or propane, offering flexibility in fuel choice depending on availability and preference. Their engineering is optimized for minimal fuel consumption while maximizing output, making them a cost-effective solution for power needs.

Furthermore, these models incorporate advanced monitoring and control systems. Users can conveniently monitor generator performance and status through an intuitive mobile app or control panel. This technology allows users to receive alerts and updates, ensuring they are always informed about the power situation at their location.

Noise reduction technology is also a key characteristic of this series. Generac's engineers have focused on minimizing sound output, providing a quieter operation compared to many other generators in the market. This feature is particularly beneficial for residential areas where noise can be a significant concern.

Overall, the Generac 004702-0, 004703-0, 004704-0, 004705-0, 004706-0, and 004707-0 models exemplify reliability, efficiency, and advanced engineering. Their comprehensive features and user-friendly technology make them an excellent choice for anyone seeking a dependable backup power solution.