Generac Power Systems 005221-0 owner manual START-UP Checklist, ‹ Preparation for START-UP

Models: 005221-0

1 60
Download 60 pages 31.75 Kb
Page 14
Image 14

Standby Generator Sets

Installation

START-UP CHECKLIST

Before working on the generator, ensure the fol- lowing:

The AUTO/OFF/MANUAL switch is in the OFF position.

The 120VAC supply to the battery charger is switched OFF.

‹PREPARATION FOR START-UP

Ensure that the 120VAC circuit breaker to the bat- tery charger is open.

Remove the fuse from the the control panel. For the H-100 and R-100: Open the front door of the control box and remove the 15 Amp ATO fuse in the lower left-hand corner of the control box.

Connect the battery cables to the battery. Attach negative battery cable last.

Close the 120VAC circuit breaker to the battery charger.

Measure the voltage at the battery before and after the charger is turned on.

Verify all AC electrical connections are tight at the circuit breaker and transfer switch.

Visually inspect entire area looking for loose paper, plastic wrappings, leaves, etc.

Check all hoses clamps fittings for leaks or dam- age.

Check all electrical plugs throughout the genera- tor. Ensure each plug is seated correctly and fully inserted into its receptacle.

Verify the AUTO/OFF/MANUAL switch is in OFF position.

Open the valve to the engine fuel line.

Bleed the fuel system of air. (necessary for long fuel lines).

Open the generator main line circuit breaker.

Connect a manometer to the gas line and record the static pressure. It must be as listed in the Specifications.

Insert the fuse into the control panel.

Move the AUTO/OFF/MANUAL switch to the MAN- UAL position. The engine should now crank and start.

Check voltage at the generator terminals.

For 3-phase units, check phase rotation at the transfer switch terminals. The generator phase rotation must match the utility phase rotation.

Check for coolant, fuel, oil, and exhaust leaks.

Close the generators main line circuit breaker.

Turn the generator set off.

Connect the UTILITY supply to the transfer switch.

Set the AUTO/OFF/MANUAL switch to AUTO.

Disconnect utility power before the transfer switch.

Engine should start, transfer to load.

Run at least 15 minutes on generator power. Make certain all 3-phase loads are functioning correctly (correct phase rotation).

Reconnect Utility power

Transfer switch will transfer back to Utility and engine will shut down within the given time parameters set up for the specific transfer switch and controller.

Install all covers, access plates and door panels.

Put the Owners Manual in a safe and accessible place.

Make certain the AUTO/OFF/MANUAL switch is in the AUTO position.

‹START-UP INSPECTION

When a start-up is performed by an Authorized Service Dealer, a standard three-part form titled “Start-up Inspection for Standby Power Systems” (part no. 067377), should be completed by the instal- lation technician or engineer. See page 1-3 for infor- mation on locating the nearest Authorized Service Dealer. The installer should complete the form and disseminate copies as follows:

White copy: Mail to Generac Warranty Department, P.O. Box 340, 211 Murphy Dr., Eagle, WI 53119- 2062.

Pink Copy: For service file of installing dealer.

Yellow Copy: For the customer’s records.

11/05 A .Rev Install001

8-2

Page 14
Image 14
Generac Power Systems 005221-0 owner manual START-UP Checklist, ‹ Preparation for START-UP, ‹ START-UP Inspection

005221-0 specifications

Generac Power Systems 005221-0 is a highly reliable portable generator that stands out in the market for its efficiency and advanced features. Designed for both home and recreational use, this generator delivers power when it's needed most, ensuring that users can stay connected and maintain their activities during power outages or job sites without electricity.

One of the main features of the Generac 005221-0 is its robust engine design. It is powered by a reliable OHV (Overhead Valve) engine that offers a consistent power output while maintaining fuel efficiency. This design ensures that the generator can run for extended periods, making it perfect for emergency situations or outdoor events.

The generator boasts a versatile power output, with a maximum capacity of 3,500 running watts and 4,500 starting watts. This level of output allows it to handle essential appliances like refrigerators, lights, and sump pumps, as well as power tools and other higher-demand equipment. The inclusion of multiple outlets, including both 120V and 30A twist-lock outlets, provides flexibility in power distribution, catering to different user needs.

One notable technology incorporated in the Generac 005221-0 is the PowerRush Technology, which offers an extra boost of power for starting larger appliances. This means that users can simultaneously power multiple devices without experiencing any performance dips. Furthermore, the generator is equipped with features that enhance user convenience, including an easy-to-read LED dashboard that displays key information such as power output and oil levels.

Durability and portability are other key characteristics of this generator. It features a compact and lightweight design combined with a sturdy frame and rubberized handle for easy transport. The never-flat wheels ensure that it can be moved easily across various terrains, making it suitable for job sites, camping trips, and other outdoor uses.

In terms of safety, the Generac 005221-0 is designed with an integrated circuit breaker to prevent overloads, as well as a low-oil shutdown feature that stops the engine when oil levels are critically low. This ensures that the generator operates safely and extends its lifespan.

Overall, the Generac Power Systems 005221-0 is an excellent choice for those in need of a dependable, efficient, and versatile portable generator. Its combination of innovative technology, robust features, and user-friendly design makes it a valuable asset for any home or outdoor enthusiast.