START-UP CHECKLIST
A. Preliminary Information
OUTDOOR: MODEL NO. |
|
| SERIAL | NO. |
| ||||
INDOOR: AIR HANDLER MANUFACTURER |
|
|
|
|
|
| |||
MODEL NO. |
|
| SERIAL | NO. |
| ||||
ADDITIONAL ACCESSORIES |
|
|
|
|
|
|
B. Pre-Start-Up
OUTDOOR UNIT |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
IS THERE ANY SHIPPING DAMAGE? |
|
|
|
| (Y/N) |
|
|
|
|
| |||||
IF SO, WHERE: |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
WILL THIS DAMAGE PREVENT UNIT |
| (Y/N) |
|
|
|
|
|
|
|
|
|
| |||
CHECK POWER SUPPLY. DOES IT AGREE WITH UNIT? | (Y/N) |
|
|
| |||||||||||
HAS THE GROUND WIRE BEEN CONNECTED? | (Y/N) |
|
|
|
|
|
|
|
|
|
|
| |||
HAS THE CIRCUIT PROTECTION BEEN SIZED AND INSTALLED PROPERLY? | (Y/N) |
|
| ||||||||||||
ARE THE POWER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY? | (Y/N) |
|
|
HAVE COMPRESSOR HOLDDOWN BOLTS BEEN LOOSENED (Snubber washers are snug, but not tight)?
(Y/N) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CONTROLS |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
ARE THERMOSTAT AND INDOOR FAN CONTROL WIRING |
|
|
|
|
|
|
|
|
| ||||||||||
CONNECTIONS MADE AND CHECKED? | (Y/N) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
ARE ALL WIRING TERMINALS (including main power supply) TIGHT? | (Y/N) |
|
|
|
|
|
| ||||||||||||
HAS CRANKCASE HEATER BEEN ENERGIZED FOR 24 HOURS? | (Y/N) |
|
|
|
|
| |||||||||||||
INDOOR UNIT |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE? | (Y/N) |
|
|
| |||||||||||||||
ARE PROPER AIR FILTERS IN PLACE? | (Y/N) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
HAVE FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENT? | (Y/N) |
|
|
| |||||||||||||||
DO THE FAN BELTS HAVE PROPER TENSION? | (Y/N) |
|
|
|
|
|
|
|
|
|
|
| |||||||
HAS CORRECT FAN ROTATION BEEN CONFIRMED? |
| (Y/N) |
|
|
|
|
|
|
|
|
| ||||||||
PIPING |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
ARE LIQUID LINE SOLENOID VALVES LOCATED AT THE INDOOR COILS AS REQUIRED? | (Y/N) |
HAVE LEAK CHECKS BEEN MADE AT COMPRESSOR, OUTDOOR AND INDOOR COILS,
TXVs (Thermostatic Expansion Valves), SOLENOID VALVES, FILTER DRIERS, AND FUSIBLE PLUGS
WITH A LEAK DETECTOR? | (Y/N) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
LOCATE, REPAIR, AND REPORT ANY LEAKS. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
HAVE ALL COMPRESSOR SERVICE VALVES BEEN FULLY OPENED (BACKSEATED)? | (Y/N) | ||||||||||||||||||||||
HAVE LIQUID LINE SERVICE VALVES BEEN OPENED? | (Y/N) |
|
|
|
|
|
|
|
|
| |||||||||||||
IS THE OIL LEVEL IN EACH COMPRESSOR CRANKCASE VISIBLE IN THE COMPRESSOR SIGHT GLASSES? | |||||||||||||||||||||||
(Y/N) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CHECK VOLTAGE IMBALANCE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
AB |
| V | AC |
|
| V |
|
| BC |
| V |
|
|
| |||||||||
(AB + AC + BC)/3 = AVERAGE VOLTAGE = |
|
|
|
| V |
|
|
|
|
|
|
|
|
| |||||||||
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE = |
|
|
|
| V |
|
|
|
| ||||||||||||||
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) = |
|
| % |
|
| ||||||||||||||||||
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM! |
|
|
|
| |||||||||||||||||||
CALL LOCAL POWER COMPANY FOR ASSISTANCE. |
|
|
|
|
|
|
|
|
|
|
|
|