Table 1B Ð Physical Data (SI, 60 Hz)

UNIT 38AKS

013

014

 

016

024

OPERATING WEIGHT (kg)

 

 

 

 

 

With Aluminum-Fin Coil

332

353

 

358

408

With Copper-Fin Coil

374

417

 

421

472

REFRIGERANT*

 

R-22

 

Shipping Charge (kg)

0.95

1.40

 

1.40

1.40

Operating Charge, Typical (kg)²

10.0

10.4

 

10.4

12.7

COMPRESSOR

 

Reciprocating, Semi-Hermetic

 

Model

06DD824

06DD328

 

06DD537

06EA250

No. Cylinders

6

6

 

6

4

Speed (r/s)

 

29.2

 

 

Capacity Steps

 

 

 

 

 

Accessory

33**,66,100

33**,66,100

 

33**,66,100

Ð

Standard

66,100

66,100

 

66,100

50,100

Crankcase Heater Watts

 

125

 

 

Unloader Setting (kPa)

 

 

 

 

 

Load

 

483 ±

 

6.9

 

Unload

 

414 ± 13.8

 

OIL CHARGE (L)

4.73

4.73

 

4.73

7.33

CONDENSER FANS

 

Axial Flow, Direct Drive

 

Quantity...Diameter (mm)

 

2...660

 

Nominal kW

 

0.37

 

 

Nominal Air¯ow (L/s, total)

 

5566

 

Speed (r/s)

 

17.9

 

 

Watts (total)

 

1460

 

CONDENSER COIL

 

Copper Tubes, Aluminum Fins

 

Rows...Fins/m

2...590

3...590

 

3...590

3...590

Total Face Area (sq m)

2.71

2.71

 

2.71

2.71

Storage Capacity (kg)²²

12.3

18.3

 

18.1

18.1

CONTROLS

 

 

 

 

 

Pressurestat (kPa)

 

 

 

 

 

High Pressure

 

 

 

 

 

Cutout

 

2724 ±

69

 

Cut-in

 

2034 ± 138

 

Low Pressure

 

 

 

 

 

Cutout

 

186 ±

28

 

Cut-in

 

462 +

48

 

FAN CYCLING CONTROLS

 

 

 

 

 

No 2 Fan:

 

 

 

 

 

Close (kPa)

 

1758 ± 69

 

Open (kPa)

 

1103 ± 69

 

PRESSURE RELIEF

 

Fusible Plug

 

Location

Compressor

Compressor

 

Compressor

Liquid Line

Temperature (C)

93.3

93.3

 

93.3

98.9

PIPING CONNECTIONS (in. ODM)

 

 

 

 

 

Suction

11¤8

13¤8

 

13¤8

15¤8

Liquid

 

5¤8

 

 

Hot Gas Stub

 

3¤8

 

 

*Unit is factory supplied with holding charge only.

²With 7.6 m of interconnecting piping. Operating charge is approximate for maximum system capacity. **Indicates capacity step (%) with electric unloader accessory.