Table 6B Ð Electrical Data (3 Ph/50 Hz)

 

 

 

 

 

UNIT

 

 

 

COMPR

FAN MOTORS 230 v (Single Phase)

UNIT

 

 

Volts

 

 

 

 

MOCP

 

 

Total

FLA (ea)

 

38AKS

Model

 

 

Supplied*

MCA

ICF

(Fuse

RLA

LRA

 

Fan No.

kW

Nameplate

Fans

 

 

 

 

 

 

 

 

Only)

 

 

 

 

 

 

 

 

Min

 

Max

 

 

 

 

1

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

013

803

230

 

198

 

264

47.5

134

75

32.9

128

2

2.9

 

3.5

1.20

903

400

 

342

 

457

31.4

80

50

20.0

74

 

 

 

 

 

 

 

 

 

014

803

230

 

198

 

264

51.0

149

75

35.7

143

2

2.9

 

3.5

1.20

903

400

 

342

 

457

34.0

89

50

22.1

83

 

 

 

 

 

 

 

 

 

016

803

230

 

198

 

264

66.9

206

100

47.9

200

2

2.9

 

3.5

1.20

903

400

 

342

 

457

43.0

121

60

29.3

115

 

 

 

 

 

 

 

 

 

024

803

230

 

198

 

254

91.8

213

150

67.9

207

 

 

 

 

 

303

346

 

311

 

380

51.5

121

80

33.3

115

2

2.9

 

3.5

1.20

 

903

400

 

342

 

440

50.2

179

80

34.6

173

 

 

 

 

 

 

LEGEND

*Units are suitable for use on electrical systems where voltage sup-

FLA

Ð Full Load Amps (Fan Motors)

plied to the unit terminals is not below or above the listed limits.

 

ICF

Ð Maximum Instantaneous Current Flow during start-up

NOTES:

 

(LRA of compressor plus total FLA of fan motors)

1. The MCA and MOCP values are calculated in accordance

kW

Ð Total Fan Motor Input (kilowatts)

with the National Electrical Code (NEC) article 440 (U.S.A.

LRA

Ð Locked Rotor Amps

standard).

MCA

Ð Minimum Circuit Amps per NEC (U.S.A.),

2. Motor RLA and LRA values are established in accordance

 

Section 430-24

with Underwriters' Laboratories (UL) Standard 1995 (U.S.A.

MOCP Ð Maximum Overcurrent Protection (amps)

standard).

RLA

Ð Rated Load Amps (Compressor)

 

PRE-START-UP

IMPORTANT: Before beginning Pre-Start-Up or Start-Up, review Start-Up Checklist at the back of this book. The Checklist assures proper start-up of a unit and provides a record of unit condition, application re- quirements, system information, and operation at ini- tial start-up.

Do not attempt to start the condensing unit, even momentarily, until the following steps have been com- pleted. Compressor damage may result.

System Check

1.Check all air handler(s) and other equipment auxiliary com- ponents. Consult the manufacturer's instructions regard- ing any other equipment connected to the condensing unit. If unit has ®eld-installed accessories, be sure all are prop- erly installed and correctly wired. If used, air¯ow switch must be properly installed.

2.Backseat (open) compressor suction and discharge valves. Now close valves one turn to allow refrigerant pressure to reach test gages.

3.Open liquid line service valve.

4.Check tightness of all electrical connections.

5.Compressor oil level should be visible in sight glass. See Fig. 9. Adjust the oil level as required. Refer to Pre- liminary Oil Charge section. No oil should be removed unless the crankcase heater has been energized for at least 24 hours.

6.Be sure unit is properly leak checked, dehydrated, and charged. See Preliminary Charge, this page.

7.Electrical power source must agree with nameplate rating.

8.Crankcase heater must be ®rmly locked into compressor crankcase. Be sure crankcase is warm (heater must be on for 24 hours before starting compressor).

9.Be sure compressor ¯oats freely on the mounting springs and that snubber washers can be moved with ®nger pres- sure. See Compressor Mounting, page 8, and Fig. 3 for loosening compressor bolts.

Leak Test and Dehydration Ð Leak test the entire refrigerant system using soap bubbles and/or an electronic leak detector. Evacuate and dehydrate entire refrigerant sys- tem by use of methods described in GTAC II, Module 4, System Dehydration.

Turn On Crankcase Heater Ð Turn on crankcase heater for 24 hours before starting the unit to be sure all the refrigerant is out of the oil. To energize the crankcase heater, proceed as follows:

1.Set the space thermostat set point above the space tem- perature so there is no demand for cooling.

2.Close the ®eld disconnect.

3.Turn the fan circuit breaker on. Leave the com- pressor circuit breakers off. The crankcase heater is now energized.

Preliminary Charge Ð Refer to GTAC II, Module 5, Charging, Recovery, Recycling, and Reclamation for charg- ing methods and procedures. Charge each system with R-22 by the liquid charging method (through liquid service valve) on the high side. Charge according to the values in the Charging Chart, Fig. 10, 11, or 12.

12

Page 12
Image 12
Carrier 38AKS013-024 specifications Pre-Start-Up, System Check, Ð Electrical Data 3 Ph/50 Hz, Mca Icf

38AKS013-024 specifications

The Carrier 38AKS013-024 is a prominent series of packaged air conditioning units designed to achieve optimal performance across various applications. Engineered with advanced technologies, these units are ideal for both residential and light commercial spaces, offering reliable climate control in a compact design.

The main features of the Carrier 38AKS series include high-efficiency cooling and heating capabilities. With SEER ratings that meet or exceed industry standards, these units offer reduced energy consumption, making them an environmentally friendly choice. Furthermore, the Carrier 38AKS013-024 is equipped with a scroll compressor, which enhances reliability and reduces operating noise, creating a more comfortable indoor environment.

One of the standout technologies incorporated in the Carrier 38AKS series is its advanced microprocessor control system. This technology provides precise temperature control and allows for easy integration with smart home systems. Users can conveniently manage their indoor climate through remote access, ensuring comfort at all times.

Additionally, the 38AKS series boasts durable construction materials, ensuring longevity and sustained performance even in challenging environmental conditions. The units feature a galvanized steel cabinet with a rust-resistant finish, providing protection from the elements. This design also allows for easy access to internal components during maintenance, simplifying servicing.

In terms of characteristics, the Carrier 38AKS013-024 offers a range of cooling capacities, making it suitable for various space sizes and applications. The lightweight design facilitates easy installation, while the low noise levels ensure minimal disruption in residential settings. These units also come with environmentally friendly refrigerants, aligning with modern sustainability goals.

Carrier's commitment to quality and performance is evident in the 38AKS series. With their combination of innovative technology, energy efficiency, and robust construction, the Carrier 38AKS013-024 units represent an excellent choice for those seeking a reliable and efficient air conditioning solution. Whether for home or light commercial use, these units promise consistent comfort and satisfaction.