![Table 2 Ð Weight Distribution](/images/new-backgrounds/33850/3385015x1.webp)
Table 2 Ð Weight Distribution
|
|
|
|
|
|
|
|
| WEIGHT |
|
|
|
|
|
|
|
|
| ||
UNIT | Total |
|
|
|
|
|
| Support Point |
|
|
|
|
|
|
| |||||
38AKS | Operating |
| A |
| B |
| C | D |
|
| E |
| F | |||||||
| lb | kg | lb |
| kg | lb |
| kg | lb |
| kg | lb |
| kg | lb |
| kg | lb |
| kg |
013 | 732 | 332 | 94 |
| 43 | 93 |
| 42 | 93 |
| 42 | 149 |
| 68 | 151 |
| 68 | 152 |
| 69 |
013C | 825 | 374 | 119 |
| 54 | 116 |
| 53 | 115 |
| 52 | 157 |
| 71 | 159 |
| 72 | 159 |
| 72 |
014 | 779 | 353 | 95 |
| 43 | 94 |
| 43 | 94 |
| 43 | 164 |
| 74 | 166 |
| 75 | 166 |
| 75 |
014C | 919 | 417 | 131 |
| 59 | 129 |
| 59 | 128 |
| 58 | 176 |
| 80 | 177 |
| 80 | 178 |
| 81 |
016 | 789 | 358 | 95 |
| 43 | 95 |
| 43 | 96 |
| 44 | 167 |
| 76 | 168 |
| 76 | 168 |
| 76 |
016C | 929 | 421 | 131 |
| 59 | 130 |
| 59 | 130 |
| 59 | 178 |
| 81 | 180 |
| 82 | 180 |
| 82 |
024 | 900 | 408 | 119 |
| 54 | 114 |
| 52 | 113 |
| 51 | 179 |
| 81 | 185 |
| 84 | 190 |
| 86 |
024C | 1040 | 472 | 155 |
| 70 | 150 |
| 68 | 146 |
| 66 | 191 |
| 87 | 196 |
| 89 | 202 |
| 92 |
Step 2 Ð Rig and Mount the Unit
Be sure unit panels are securely in place prior to rigging.
RIGGING Ð These units are designed for overhead rigging only. For this purpose, the transverse base channels extend beyond the sides of the unit, with holes provided in the end plates to attach cables or hooks. Rig with top skid packaging assembly in place to prevent unit damage by the rigging cable. As further protection for the coil faces, plywood sheets can be placed against the sides of the unit, behind the cables. Run the cables to a central suspension point so that the angle from the horizontal is not less than 45 degrees. Raise and set the unit down carefully.
If it is necessary to roll the unit into position, mount the unit on longitudinal rails, using a minimum of 3 rollers. Apply force to the rails, not the unit. If the unit is to be skid- ded into position, place it on a large pad and drag it by the pad. Do not apply any force to the unit.
Raise from above to lift unit from the rails or pad when unit is in ®nal position.
COMPRESSOR MOUNTING Ð As shipped, the compres- sor is held tightly in place by
Step 3 Ð Complete Refrigerant Piping Connections
IMPORTANT: A refrigerant receiver is not provided with the unit. Do not install a receiver.
SIZE REFRIGERANT LINES Ð Consider the length of pip- ing required between outdoor unit and indoor unit (evapo- rator), the amount of liquid lift, and compressor oil return. See Tables
NOTE: Use the piping data in Tables
Condensing units with
Note that refrigerant suction piping should be insulated.
Table 3 Ð Liquid Line Data
| MAXIMUM |
|
|
| ||
| ALLOWABLE |
| LIQUID LINE | |||
| LIQUID LIFT |
| ||||
|
|
|
| |||
UNIT | ft (m) |
|
|
| ||
38AKS |
|
| Maximum | Maximum | Filter Drier | |
|
| Allowable | Allowable | and | ||
|
|
| ||||
| 60 Hz | 50 Hz | Pressure | Temp. | Sight Glass | |
|
|
| Drop | Loss | Flare Conn.* | |
|
|
| psig (kPa) | F (C) | in. (mm) | |
013 | 52 (15.8) |
|
|
| ||
014 | 67 (20.4) | 7 (48.3) | 2 (1.1) | 5¤8 (15.88) | ||
016 | 82 (25.0 | |||||
|
|
| ||||
024 | 87 (26.5) | 86 (26) |
|
|
| |
|
|
|
|
|
|
*Inlet and outlet.
NOTE: Data shown is for units operating at 45 F (7.2 C) saturated suction and 95 F (35 C) entering air.
Fig. 3 Ð Compressor Mounting
8