Carrier 38AKS013-024 Ð Rig and Mount the Unit, Ð Complete Refrigerant Piping Connections

Models: 38AKS013-024

1 24
Download 24 pages 21.22 Kb
Page 8
Image 8
Table 2 Ð Weight Distribution

Table 2 Ð Weight Distribution

 

 

 

 

 

 

 

 

 

WEIGHT

 

 

 

 

 

 

 

 

 

UNIT

Total

 

 

 

 

 

 

Support Point

 

 

 

 

 

 

 

38AKS

Operating

 

A

 

B

 

C

D

 

 

E

 

F

 

lb

kg

lb

 

kg

lb

 

kg

lb

 

kg

lb

 

kg

lb

 

kg

lb

 

kg

013

732

332

94

 

43

93

 

42

93

 

42

149

 

68

151

 

68

152

 

69

013C

825

374

119

 

54

116

 

53

115

 

52

157

 

71

159

 

72

159

 

72

014

779

353

95

 

43

94

 

43

94

 

43

164

 

74

166

 

75

166

 

75

014C

919

417

131

 

59

129

 

59

128

 

58

176

 

80

177

 

80

178

 

81

016

789

358

95

 

43

95

 

43

96

 

44

167

 

76

168

 

76

168

 

76

016C

929

421

131

 

59

130

 

59

130

 

59

178

 

81

180

 

82

180

 

82

024

900

408

119

 

54

114

 

52

113

 

51

179

 

81

185

 

84

190

 

86

024C

1040

472

155

 

70

150

 

68

146

 

66

191

 

87

196

 

89

202

 

92

Step 2 Ð Rig and Mount the Unit

Be sure unit panels are securely in place prior to rigging.

RIGGING Ð These units are designed for overhead rigging only. For this purpose, the transverse base channels extend beyond the sides of the unit, with holes provided in the end plates to attach cables or hooks. Rig with top skid packaging assembly in place to prevent unit damage by the rigging cable. As further protection for the coil faces, plywood sheets can be placed against the sides of the unit, behind the cables. Run the cables to a central suspension point so that the angle from the horizontal is not less than 45 degrees. Raise and set the unit down carefully.

If it is necessary to roll the unit into position, mount the unit on longitudinal rails, using a minimum of 3 rollers. Apply force to the rails, not the unit. If the unit is to be skid- ded into position, place it on a large pad and drag it by the pad. Do not apply any force to the unit.

Raise from above to lift unit from the rails or pad when unit is in ®nal position.

COMPRESSOR MOUNTING Ð As shipped, the compres- sor is held tightly in place by self-locking bolts. Before start- ing unit, loosen self-locking bolts until the snubber washer can be moved sideways with ®nger pressure. Do not remove shipping bolts. See Fig. 3.

Step 3 Ð Complete Refrigerant Piping Connections

IMPORTANT: A refrigerant receiver is not provided with the unit. Do not install a receiver.

SIZE REFRIGERANT LINES Ð Consider the length of pip- ing required between outdoor unit and indoor unit (evapo- rator), the amount of liquid lift, and compressor oil return. See Tables 3-5B and also refer to Part 3 of Carrier System Design Manual and E20-II software for design details and line sizing. Refer to indoor unit installation instructions for additional information.

NOTE: Use the piping data in Tables 3-5B as a general guide only. For more precise calculations, refer to Carrier System Design manual or E20-II software.

Condensing units with multiple-step unloading may require double suction risers to assure proper oil return at minimum load operating condition. See Tables 4A-5B and Fig. 4. Reduction of evaporator coil surface should be ana- lyzed to provide sufficient refrigerant velocity to return oil to the compressor. Liquid line solenoid valves may be used in certain situations to accomplish this. Hot gas bypass, if used, should be introduced before the evaporator.

Note that refrigerant suction piping should be insulated.

Table 3 Ð Liquid Line Data

 

MAXIMUM

 

 

 

 

ALLOWABLE

 

LIQUID LINE

 

LIQUID LIFT

 

 

 

 

 

UNIT

ft (m)

 

 

 

38AKS

 

 

Maximum

Maximum

Filter Drier

 

 

Allowable

Allowable

and

 

 

 

 

60 Hz

50 Hz

Pressure

Temp.

Sight Glass

 

 

 

Drop

Loss

Flare Conn.*

 

 

 

psig (kPa)

F (C)

in. (mm)

013

52 (15.8)

 

 

 

014

67 (20.4)

7 (48.3)

2 (1.1)

5¤8 (15.88)

016

82 (25.0

 

 

 

024

87 (26.5)

86 (26)

 

 

 

 

 

 

 

 

 

*Inlet and outlet.

NOTE: Data shown is for units operating at 45 F (7.2 C) saturated suction and 95 F (35 C) entering air.

Fig. 3 Ð Compressor Mounting

8

Page 8
Image 8
Carrier 38AKS013-024 Ð Rig and Mount the Unit, Ð Complete Refrigerant Piping Connections, Ð Weight Distribution