| LEGEND |
EQUIP GND Ð Equipment Ground | |
NEC | Ð National Electrical Code |
Factory Wiring
Field Wiring
Fig. 7 Ð Main Power Supply Wiring
LEGEND
CÐ Compressor Contactor
HD | Ð Heating Device | |
IFC | Ð | |
LLSV1 Ð Liquid Line Solenoid Valve 1 Ð Refrigerant Migration | ||
LLSV2 Ð | Control | |
Liquid Line Solenoid Valve 2 Ð Capacity Control |
RÐ Relay
Factory Wiring
Field Wiring
NOTES:
1.Combination LLSV plus IFC va should not exceed 30 va.
2.Do not exceed 5 va (24 vac) per coil.
3.If va values shown in Notes 1 and 2 must be exceeded, use accessory relay transformer package 38AE900001 (60 Hz) or 38AD900003 (50 Hz and
Fig. 8 Ð Remote Thermostat Wiring
Table 6A Ð Electrical Data (3 Ph/60 Hz)
|
|
|
|
|
| UNIT |
|
|
|
|
| COMPR |
| FAN MOTORS (Single Phase) | ||||||
UNIT |
|
|
| Volts |
|
|
|
|
| MOCP |
|
|
|
| Total | FLA (ea) |
| |||
38AKS | Model |
|
| Supplied* | MCA |
| ICF | (Fuse |
| RLA |
| LRA | Fan No. | kW | ||||||
Nameplate |
|
|
|
| Fans | |||||||||||||||
|
|
|
|
|
|
|
|
|
| Only) |
|
|
|
|
|
|
| |||
|
|
|
| Min |
| Max |
|
|
|
|
|
|
| 1 | 2 |
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
| 501 |
| 187 |
| 253 | 62.5 |
| 178 | 100 |
| 43.6 |
| 170 |
|
| 4.3 | 3.7 |
| |
013 |
| 201 | 380 |
| 342 |
| 418 | 35.0 |
| 101 | 50 |
| 24.0 |
| 93 |
| 2 | 4.3 | 3.7 | 1.41 |
| 601 | 460 |
| 414 |
| 528 | 29.1 |
| 81 | 40 |
| 20.0 |
| 77 |
| 2.3 | 1.9 | |||
|
|
|
|
|
|
|
|
|
| |||||||||||
|
| 101 | 575 |
| 518 |
| 660 | 22.8 |
| 67 | 35 |
| 15.7 |
| 62 |
|
| 1.8 | 1.8 |
|
|
| 501 |
| 187 |
| 253 | 69.3 |
| 199 | 100 |
| 49.3 |
| 191 |
|
| 4.3 | 3.7 |
| |
014 |
| 201 | 380 |
| 342 |
| 418 | 38.0 |
| 112 | 60 |
| 26.5 |
| 104 |
| 2 | 4.3 | 3.7 | 1.41 |
| 601 | 460 |
| 414 |
| 528 | 31.7 |
| 84 | 50 |
| 22.1 |
| 80 |
| 2.3 | 1.9 | |||
|
|
|
|
|
|
|
|
|
| |||||||||||
|
| 101 | 575 |
| 518 |
| 660 | 25.6 |
| 73 | 40 |
| 17.9 |
| 69 |
|
| 1.8 | 1.8 |
|
|
| 501 |
| 187 |
| 253 | 87.5 |
| 274 | 125 |
| 63.6 |
| 266 |
|
| 4.3 | 3.7 |
| |
016 |
| 201 | 380 |
| 342 |
| 418 | 49.3 |
| 153 | 80 |
| 36.0 |
| 145 |
| 2 | 4.3 | 3.7 | 1.41 |
| 601 | 460 |
| 414 |
| 528 | 40.7 |
| 124 | 60 |
| 29.3 |
| 120 |
| 2.3 | 1.9 | |||
|
|
|
|
|
|
|
|
|
| |||||||||||
|
| 101 | 575 |
| 518 |
| 660 | 33.0 |
| 100 | 50 |
| 23.8 |
| 96 |
|
| 1.8 | 1.8 |
|
|
| 501 |
| 187 |
| 254 | 93.4 |
| 353 | 150 |
| 67.9 |
| 345 |
|
| 4.3 | 3.7 |
| |
024 |
| 201 | 380 |
| 342 |
| 418 | 49.7 |
| 199 | 80 |
| 34.6 |
| 191 |
| 2 | 4.3 | 3.7 | 1.41 |
| 601 | 460 |
| 414 |
| 508 | 48.1 |
| 177 | 80 |
| 34.7 |
| 173 |
| 2.3 | 1.9 | |||
|
|
|
|
|
|
|
|
|
| |||||||||||
|
| 101 | 575 |
| 518 |
| 632 | 40.1 |
| 124 | 60 |
| 28.8 |
| 120 |
|
| 1.8 | 1.8 |
|
|
|
| LEGEND |
|
|
|
|
| *Units are suitable for use on electrical systems where voltage sup- | |||||||||||
FLA | Ð Full Load Amps (Fan Motors) |
|
|
|
|
| plied to the unit terminals is not below or above the listed limits. | |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
ICF | Ð Maximum Instantaneous Current Flow during |
| NOTES: |
|
|
|
|
|
| |||||||||||
|
| (LRA of compressor plus total FLA of fan motors) |
| 1. The MCA and MOCP | values are calculated in accordance | |||||||||||||||
kW | Ð Total Fan Motor Input (kilowatts) |
|
|
|
|
|
| with the National Electrical Code (NEC) article 440 (U.S.A. | ||||||||||||
LRA | Ð Locked Rotor Amps |
|
|
|
|
|
|
|
| standard). |
|
|
|
|
|
| ||||
MCA | Ð Minimum Circuit Amps per NEC (U.S.A.), |
|
|
| 2. Motor RLA | and LRA values are established in accordance | ||||||||||||||
|
| Section |
|
|
|
|
|
|
|
| with Underwriters' Laboratories (UL) Standard 1995 (U.S.A. | |||||||||
MOCP Ð Maximum Overcurrent Protection (amps) |
|
|
|
| standard). |
|
|
|
|
|
| |||||||||
RLA | Ð Rated Load Amps (Compressor) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
11