6
1PROGRAMMING LIMITS & FORCE
(Continuing from Installation Poster if provided)
SETTING & TESTING LIMITS AND FORCE
The OPEN (UP) and CLOSE (DOWN) Door Limit positions are controlled by making adjustments using the panel located on the bottom of the powerhead. Begin with Step 1 and continue through Step 10. Door Force is set during the final Open/Close cycle of these steps. The powerhead will automatically set door speed at slow if the distance between limits is less than 6 feet. Once Limits and Force are set DO NOT use the or buttons to open or close door.
WARNING
sMake sure doorway is in view and clear of obstacles and people to avoid injury or damage to property.
sDO NOT operate this unit from wall console before LIMITS and FORCE are set. Severe damage to the opener can occur.
sThe bullet MUST be engaged to carriage BEFORE setting limits. See Installation Poster (if provided) or refer to pages 11 and 19.
©2011 The Genie Company
A) CLOSE DOOR TRAVEL LIMIT
NOTE: If bullet has NOT been engaged to the carriage, do so now.
Please note that there is a 30 second timeout between each programming step.
A programming timeout during these steps has occured when two RED flashing LEDs appear.
In the event of a timeout please restart at Step 1.
1PRESS and HOLD
PROGRAM | SET | — | + |
|
| ||
|
|
|
SEE BOTH Blue LEDs come ON
2
RELEASE
SEE round
Blue LED come ON
3PRESS and RELEASE
PROGRAM | — | + |
|
|
SEE long Blue
LED come ON
If RED LED comes ON - STOP and
exit programming.
3/2011
4NOTE: If one or both LEDs come ON RED at this time, Limits programming menu was not entered properly. You must exit programming and restart.
To exit the programming function wait 30 seconds for the programming to time out.
| PROGRAM | SET | — |
PRESS and |
| ||
|
| ||
RELEASE |
|
|
|
SEE round Blue
LED flashing
5PRESS and HOLD until door is FULLY CLOSED then RELEASE
RAM |
|
|
|
G |
| — | + |
|
| ||
| SE |
| |
|
|
|
Watch door move
OT
CE
NOTE: You can start and stop door
movement using either buttons until door is in correct open or closed position.