Genie LM-9, LM-6 page, Installation, Wiring The Valves, Connecting The Wires To The Controller

Models: LM-12 LM-9 LM-6

1 9
Download 9 pages 32 Kb
Page 4
Image 4
INSTALLATION

INSTALLATION

Note: LAWN MASTER is for indoor installation only. Do not plug transformer into the same outlet as other high power devices such as garage door opener, power tools, etc.

Select an indoor location near a 110 volt outlet to mount your controller. Avoid using an outlet that is controlled with an on/off switch. Mount approximately 48” from floor.

Controller should not be exposed to water or operated at temperatures below 14 deg. or above 113 deg. Fahrenheit.

Screw a No. 8 screw into wall leaving approximately 1/8” exposed. Use a plastic anchor sleeve if wall is plaster board or masonry.

Slip the keyhole in the back of the controller over the exposed screw.

Screw No. 8 screws through the holes at the bottom of the controller case to secure.

WIRING THE VALVES

Connect your valves to the controller with 20 gauge plastic jacketed wire. If distance from controller to valves is longer than 700 feet use 16 gauge.

Thermostat wire is available in 4 and 7 strand colored wires. You may bury wire in the ground being careful to avoid locations which can be disturbed by digging. Use of UF wire is recommended for underground wiring.

Extra protection is possible by pulling the wires through PVC water pipe. All wire connections should be made using water-proof connectors.

page 2

CONNECTING THE WIRES TO THE CONTROLLER

Remove lower panel covering, turn up and over. Line up terminal identification area with terminal screws as shown below.

Connect the wire from valve number 1 to terminal slot number 1, connect the wire

from valve number 2 to terminal slot number 2 and so on until all valves are

 

connected. Connect the COMMON wire from the valves to the terminal marked

 

COMM.

 

 

 

 

If using a MASTER VALVE or PUMP START, see below.

 

 

-Back side of lower panel

 

 

 

 

-Terminal identification area

I

-

-

I

-Terminals

 

 

 

 

Master Valve Pump Start Hook-Up

In cases where a pump is to controlled by the Master Valve output, DO NOT drive the pump directly from the controller. The Master Valve Terminal must be connected to the coil of a 24 VAC relay. (Lawn Genie Pump Relays are relay part no. L3OOOOW)

The pump latch relay should be set up by an electrician so that a switch closure will activate the latch relay coil, turning on the pump. The switch contacts of the relay should be connected to control the latch relay coil, see figure. The relay should be mounted at least 5 feet from the controller, and the box must be grounded.

Installation must follow all local electrical wiring codes. Make sure master valve is selected as needed in all your

programs. Refer to watering duration (page 5)

Caution: Do not attempt to power the controller using power from one phase of pump power. This will damage the controller, the pump or both.

INSTALL BATTERY

LAWN MASTER is protected from time loss with a back-up battery (install the battery after the transformer is connected.) Battery will maintain time and day up to 60 days during a power failure. Install 9 volt alkaline battery as shown. (Battery not included).

Note: Battery will not operate valves during a power outage.

II

TRANSFORMER CONNECTION

Make sure transformer is disconnected from power outlet. Connect the two lead wires from the transformer to terminals as shown.

First (2) terminal locations: 24 VAC

Plug- in transformer, check operation.