25
APPENDIX A BLOWER PERFORMANCE DATA
BELT DRIVE - STANDARD DOWN SHOT
CPG090 STANDARD BELT DRIVE DO WN SHOT
CFM RPM BHP CFM RPM B HP CFM RPM BHP CF M RPM BHP CFM RPM BHP CFM RPM BHP
0.1 3522 750 1.14 3228 706 0.94 2964 661 0.73
0.3 3337 800 1. 19 3102 756 1 2800 706 0 .76 2504 661 0. 59
0.5 3387 84 4 1.32 2834 8 06 0.9 9 2603 757 0.8
0.7 3453 89 3 1.5 2903 85 0 1.12
0.9 2957 89 9 1.29
CPG102 STANDARD BELT DRIVE DO WN SHOT
CFM RPM BHP CFM RPM B HP CFM RPM BHP CF M RPM BHP CFM RPM BHP CFM RPM BHP
0.1 3372 747 1.11 3078 703 0.91 2814 658 0.70
0.3 3187 797 1.16 2952 753 0.97 2650 703 0.73
0.5 3237 84 1 1.29 2684 8 03 0.9 6 2453 754 0.7 7
0.7 3303 89 0 1.47 2753 84 7 1.09
0.9 2807 89 6 1.26
CPG120 STANDARD BELT DRIVE DO WN SHOT
CFM RPM BHP CFM RPM B HP CFM RPM BHP CF M RPM BHP CFM RPM BHP CFM RPM BHP
0.2 4316 7 80 1.5
7
4118 738 1.3
6
3771 68
7
1.0
8
3376 644 0.8
5
0.4 4282 830 1. 76 3928 786 1.4 3595 7 40 1.1
3
0.6 4232 87 4 1.87 3872 83 0 1.52 3444 7 86 1.2
0.8 3839 88 0 1.64 3367 83 6 1.27
13326 885 1.4
1.2
ESP, In
H2O
TURNS OPEN
012345
TURNS OPEN
ESP, In
H2O450123
ESP, In
H2O
TURNS OPEN
012345
CPG150 STAND ARD B ELT DR IVE DO WN SH OT
ESP (IN
W.C.) CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2 5514 2.92 5604 3. 22 5064 2.16 477 5 1.81 4514 1.49 42 71 1.23
0.4 5279 2.74 5110 2. 40 4696 1.94 444 7 1.63 4123 1.31
0.6 5185 2.67 4813 2. 20 4352 1.74 403 9 1.43
0.8 4766 2.3 7 4526 2. 02
1.0 4223 2.01
0 TURNS 1 TURN 2 TURNS 3 TURNS 4 TURNS 5 TURNS
NOTE: High Static airflow requires installation of High Static Kit (HSKT*), or factory-built High Static model. Unit factory shipped at 2.5 turns open.
Tables represent dry coil without filter. To compensate for filter, add 0.08" to measured E.S.P. SCFM correction for wet coil = 4%.