24
APPENDIX A BLOWER PERFORMANCE DATA
BELT DRIVE - STANDARD HORIZONTAL
NOTE: High Static airflow requires installation of High Static Kit (HSKT*), or factory-built High Static model. Unit factory shipped at 2.5 turns open.
Tables represent dry coil without filter. To compensate for filter, add 0.08" to measured E.S.P. SCFM correction for wet coil = 4%.
CPG090 STANDARD BELT DR IVE HORIZONTAL
CFM RPM BHP CFM RPM BHP CF M RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.1 3381 703 0.99 3078 659 0.78
0.3 3560 796 1.26 3271 747 1 .02 2946 703 0 .82 2604 659 0. 63
0.5 3492 841 1.36 3159 799 1. 09 2819 752 0 .86
0.7 3453 891 1.5 30 94 846 1.18
0.9 2964 896 1.29 2524 852 0.96
1.1 2537 902 1.08
CPG102 STANDARD BELT DR IVE HORIZONTAL
CFM RPM BHP CFM RPM BHP CF M RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.1 3231 700 0.96 2928 656 0.75
0.3 3410 793 1.23 3121 744 0 .99 2796 700 0 .79
0.5 3342 838 1.33 3009 796 1. 06 2669 749 0 .83
0.7 3303 888 1.47 2944 843 1.15
0.9 2814 893 1.26
CPG120 STANDARD BELT DR IVE HORIZONTAL
CFM RPM BHP CFM RPM BHP CF M RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.2 4391 737 1.48 4054 693 1 .22 3760 645 0.97
0.4 4314 781 1.61 3969 737 1 .29 3534 693 1
0.6 4255 826 1.69 3894 781 1. 38 3447 743 1 .09
0.8 4234 876 1.85 3792 832 1.47
13724 877 1. 59
1.2
ESP, In
H2O
TURNS OPEN
012345
ESP, In
H2O
TURNS OPEN
012345
ESP, In
H2O
TURNS OPEN
012345
CPG150 STANDARD BELT DRIVE HORIZO NT AL
ESP (IN
W.C.) CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.2 57623.0854852.6351402.2148551.8445131.4841971.20
0.4 55502.9152072.4448572.0344891.6441001.29
0.6 52022.6549222.2544871.8141131.45
0.8 48982.4345151.9940741.58
1.0 4549 2.20 4135 1.76
1.2 4258 2.01
0 TURNS 1 TURN 2 TURNS 3 TURNS 4 TURNS 5 TURNS