Goodman Mfg GMH95 service manual Blower Performance Specifications

Models: GMH95

1 15
Download 15 pages 2.73 Kb
Page 12
Image 12
BLOWER PERFORMANCE SPECIFICATIONS

BLOWER PERFORMANCE SPECIFICATIONS

BLOWER PERFORMANCE

(CFM & Temperature Rise vs. External Static Pressure)

Model

 

Tons AC

 

 

 

EXTERNAL STATIC PRESSURE (Inches Water Column)

 

 

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating Speed

at 0.5"

0.1

 

0.2

0.3

 

0.4

 

0.5

 

0.6

0.7

0.8

 

 

 

 

 

( As Shipped )

Speed

ESP

CFM

RISE

CFM

RISE

CFM

RISE

CFM

RISE

CFM

RISE

CFM

CFM

CFM

 

HIGH

3.0

1352

 

29

1318

30

1260

 

31

1202

 

33

1128

 

35

1044

955

853

GMH950453BXA*

MED

2.5

1214

 

32

1172

34

1123

 

35

1064

 

37

1012

 

39

938

859

741

(MED-HI)

MED-LO

2.0

997

 

40

994

40

960

 

41

923

 

43

884

 

45

817

741

611

 

LOW

1.5

757

 

52

753

52

734

 

54

704

 

56

674

 

59

620

524

438

 

HIGH

3.0

1449

 

41

1409

42

1326

 

45

1273

 

47

1201

 

49

1194

1136

1018

GMH950703BXA*

MED

2.5

1192

 

50

1172

51

1141

 

52

1094

 

54

1046

 

57

973

904

793

(MED-HI)

MED-LO

2.0

981

 

61

962

62

943

 

63

917

 

65

888

 

67

830

764

665

 

LOW

1.5

750

 

79

730

81

714

 

83

692

 

86

657

 

90

620

570

502

 

HIGH

4.0

2069

 

29

1965

30

1871

 

32

1756

 

34

1661

 

36

1549

1415

1275

GMH950704CXA*

MED

3.5

1752

 

34

1724

34

1667

 

36

1603

 

37

1488

 

40

1402

1290

1082

(MED-HI)

MED-LO

3.0

1437

 

41

1437

41

1417

 

42

1369

 

43

1320

 

45

1256

1140

984

 

LOW

2.5

1184

 

50

1177

50

1161

 

51

1132

 

52

1095

 

54

1047

928

837

 

HIGH

4.0

1970

 

40

1874

342

1757

 

45

1667

 

48

1566

 

51

1431

1334

1182

GMH950904CXA*

MED

3.5

1713

 

46

1650

48

1572

 

50

1510

 

52

1418

 

56

1313

1211

1079

(MED-HI)

MED-LO

3.0

1439

 

55

1412

56

1370

 

58

1327

 

60

1260

 

63

1166

1078

956

 

LOW

2.5

1183

 

67

1155

69

1122

 

74

1108

 

72

1062

 

75

1011

931

816

 

HIGH

5.0

2147

 

37

2114

37

2057

 

39

2030

 

39

1978

 

40

1889

1784

1713

GMH950905DXA*

MED

4.0

1675

 

47

1686

47

1640

 

48

1623

 

49

1557

 

51

1501

1455

1360

(MED-HI)

MED-LO

3.5

1489

 

53

1470

54

1436

 

55

1409

 

56

1361

 

58

1318

1243

1130

 

LOW

3.0

1307

 

61

1265

63

1234

 

64

1203

 

66

1168

 

68

1096

1053

991

 

HIGH

5.0

2134

 

46

2103

47

2029

 

48

1941

 

51

1906

 

51

1818

1733

1625

GMH951155DXA*

MED

4.0

1678

 

58

1643

60

1643

 

60

1577

 

62

1527

 

64

1489

1423

1339

(MED-HI)

MED-LO

3.5

1453

 

68

1440

68

1426

 

69

1363

 

72

1349

 

73

1314

1253

1205

 

LOW

3.0

1259

 

78

1239

79

1220

 

80

1181

 

83

1159

 

85

1118

1082

1015

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.CFM in chart is without filters(s). Filters do not ship with this furnace, but must be provided by the installer. If the furnace requires two return filters, this chart assumes both filters are installed.

2.All furnaces ship as high speed cooling and medium-speed heating. Installer must adjust blower cooling & heating speed as needed.

3.For most jobs, about 400 CFM per ton when cooling is desirable.

4.INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.

5.The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate. The shaded area indicates ranges in excess of maximum external static pressure allowed when heating. The data for 0.6" w.c. to 0.8" w.c. is shown for air conditioning purposes only.

6.The above chart is for U.S. furnaces installed at 0-2000 feet. At higher altitudes, a properly de-rated unit will have approximately the same temperature rise at a particular CFM, while the ESP at that CFM will be lower.

12

Page 12
Image 12