PACKAGE HEAT PUMP SPECIFICATIONS GPH13[42-60]M41AB

 

 

GPH1342M41*

GPH1348M41*

GPH1360M41*

 

 

 

 

 

COOLING

COOLING CAPACITY, BTUH

40000

46500

56000

CAPACITY

SEER / EER

13/11

13/11

13/10.9

 

 

 

 

 

HEATING

BTU/h (47°)

40000

45500

55500

RATING

BTU/h (17°)

21000

26000

31200

 

HSPF

7.7

8.0

8.0

UNIT

VOLTAGE (NAMEPLATE)

208/230-60-1

208/230-60-1

208/230-60-1

ELECTRICAL

AMPS

22.4

29.0

35.4

SPECIFICATION

MIN CIRCUIT AMPACITY

26.8

34.5

42.0

 

MAX OVERCURRENT PROTECTION(1)

40

50

60

COMPRESSOR

TYPE

SCROLL

SCROLL

SCROLL

 

RATED LOAD AMPS

17.9

21.8

26.4

 

LOCKED ROTOR AMPS

112

117

134

 

 

 

 

 

CONDENSER

HORSEPOWER

1/4

1/4

1/4

FAN MOTOR

RPM

1075

1075

1075

 

FULL LOAD AMPS

1.4

1.4

1.4

 

LOCKED ROTOR AMPS

2.9

2.9

2.9

 

 

 

 

 

CONDENSER FAN

BLADE DIAMETER (INCHES)

22/3

22/3

22/3

NUMBER OF BLADES

 

 

 

 

 

 

 

 

 

CONDENSER

FACE AREA (SQ. FT.)

16.83

19.24

21.04

COIL

NUMBER OF ROWS

2

2

2

 

FINS PER INCH

16

16

16

 

 

 

 

 

EVAPORATOR

HORSEPOWER - NUMBER OF SPEEDS

1/3 - 3

3/4 - 5

1 - 5

BLOWER

FULL LOAD AMPS

3.06

5.8

7.6

MOTOR

LOCKED ROTOR AMPS

4.1

---

---

 

MOTOR SPEED TAP - COOLING X-13

High

T2/T3

T2/T3

 

RPM

910

1050

1050

 

 

 

 

 

EVAPORATOR

DIAMETER X WIDTH (INCHES)

10 x 9

10 x 9

10 x 9

BLOWER

RATED SCFM COOLING

1300

1720

1800

 

MAX EXTERNAL STATIC PRESS ("w.c.)

0.5

0.5

0.5

 

 

 

 

 

EVAPORATOR

FACE AREA (SQ. FT.)

4.52

6.17

6.17

COIL

NUMBER OF ROWS

4

4

4

 

FINS PER INCH

14

14

14

GENERAL

FILTER SIZE *

25 x 25 x 1

(2) 20 x 20 x 1

(2) 20 x 20 x 1

INFORMATION

DRAIN SIZE (INCHES)

3/4"

3/4"

3/4"

 

EXPANSION DEVICE (ID/OD)

0.072/0.063

0.080/0.065

0.084/0.076

 

REFRIGERANT CHARGE R410A (OZS.)

180

190

220

 

POWER SUPPLY

3/4, 1, 1-1/4

3/4, 1, 1-1/4

3/4, 1, 1-1/4

 

CONDUIT KNOCKOUT SIZE (INCHES)

 

 

 

 

 

LOW VOLTAGE

1/2

1/2

1/2

 

CONDUIT KNOCKOUT SIZE (INCHES)

 

 

 

 

 

LO PRESSURE SWITCH

 

 

 

 

OPENS / CLOSES PSIG

22 / 50

22 / 50

22 / 50

 

HI PRESSURE SWITCH - OPENS PSIG

 

 

 

 

OPENS / CLOSES PSIG

660 / 420

660 / 420

660 / 420

 

SHIPPING WEIGHT (LBS.)

440

520

533

 

OPERATING WEIGHT (LBS.)

430

510

523

(1)Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted. * Calculated external filter size based on air velocity of 300 ft/min.

Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information. IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers

in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.

9

Page 9
Image 9