HEATING PERFORMANCE DATA

 

 

 

 

GPH13[24-42]M41*

MODEL: GPH1324M41*

 

 

EXPANDED PERFORMANCE DATA

 

HEATING OPERATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

 

MBh

28.9

27.4

25.8

24.1

23.0

22.3

20.7

19.1

16.7

15.4

14.2

13.4

12.9

11.6

10.3

9.0

7.6

6.3

 

Delta T

32.4

30.7

28.9

27.0

25.8

25.0

23.2

21.4

18.8

17.3

15.9

15.1

14.5

13.0

11.5

10.1

8.6

7.0

 

KW

2.14

2.10

2.06

2.01

1.99

1.97

1.94

1.89

2.32

2.26

2.21

2.18

2.16

2.10

2.05

2.00

1.95

1.89

 

AMPS

10.4

9.8

9.2

8.8

8.5

8.4

8.0

7.7

7.4

7.1

6.9

6.7

6.7

6.4

6.1

5.8

5.5

5.1

 

COP

3.96

3.82

3.67

3.50

3.38

3.30

3.13

2.95

2.11

1.99

1.88

1.80

1.75

1.61

1.47

1.31

1.15

0.97

 

EER

13.5

13.1

12.5

12.0

11.5

11.3

10.7

10.1

7.2

6.8

6.4

6.2

6.0

5.5

5.0

4.5

3.9

3.3

 

HI PR

379

364

350

334

326

320

308

295

283

270

260

253

249

239

230

221

213

205

 

LO PR

135

126

118

108

102

98

90

80

73

65

57

53

51

43

37

31

27

22

Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.

MODEL: GPH1330M41*

 

 

 

 

 

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

 

MBh

36.2

34.3

32.3

30.2

28.8

27.9

25.9

23.9

21.2

19.6

18.0

17.0

16.4

14.7

13.0

11.4

9.7

7.9

 

Delta T

31.9

30.2

28.4

26.6

25.4

24.6

22.9

21.1

18.7

17.3

15.9

15.0

14.4

13.0

11.5

10.0

8.6

7.0

 

KW

2.74

2.68

2.63

2.58

2.55

2.53

2.48

2.43

2.29

2.24

2.19

2.17

2.15

2.10

2.05

2.00

1.95

1.90

 

AMPS

13.6

12.7

12.0

11.4

11.1

10.9

10.4

9.9

9.6

9.2

8.9

8.7

8.6

8.2

7.8

7.5

7.0

6.5

 

COP

3.87

3.74

3.59

3.42

3.30

3.23

3.06

2.88

2.71

2.55

2.40

2.30

2.23

2.05

1.86

1.66

1.46

1.22

 

EER

13.2

12.8

12.3

11.7

11.3

11.0

10.5

9.8

9.2

8.7

8.2

7.9

7.6

7.0

6.4

5.7

5.0

4.2

 

HI PR

375

359

346

330

323

316

304

292

280

267

256

250

246

236

227

218

210

203

 

LO PR

131

122

114

105

99

95

88

78

70

63

55

51

49

42

36

30

27

21

Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.

MODEL: GPH1336M41*

 

 

 

 

 

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

 

MBh

43.0

40.7

38.3

35.8

34.2

33.1

30.8

28.4

24.4

22.6

20.8

19.6

18.9

17.0

15.0

13.1

11.2

9.2

 

Delta T

34.6

32.8

30.8

28.8

27.5

26.7

24.8

22.9

19.7

18.2

16.7

15.8

15.2

13.6

12.1

10.6

9.0

7.4

 

KW

3.10

3.04

2.98

2.92

2.89

2.86

2.81

2.75

2.36

2.31

2.26

2.24

2.22

2.17

2.12

2.07

2.02

1.97

 

AMPS

15.4

14.4

13.6

12.9

12.5

12.3

11.7

11.1

10.7

10.3

9.9

9.7

9.6

9.2

8.7

8.3

7.8

7.2

 

COP

4.06

3.92

3.76

3.58

3.46

3.39

3.21

3.02

3.03

2.86

2.69

2.57

2.50

2.29

2.08

1.85

1.62

1.36

 

EER

13.9

13.4

12.8

12.2

11.8

11.6

11.0

10.3

10.4

9.8

9.2

8.8

8.5

7.8

7.1

6.3

5.5

4.6

 

HI PR

403

386

371

355

347

340

327

314

300

287

276

269

264

254

244

234

226

218

 

LO PR

137

127

119

109

103

99

91

81

73

66

58

54

52

44

38

32

28

22

 

 

Above information is for nominal CFM and

70 degree indoor dry bulb. Instantaneous capacity listed.

 

 

 

 

 

 

 

MODEL: GPH1342M41*

 

 

 

 

 

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

 

-5

-10

 

MBh

50.3

47.6

44.8

41.9

40.0

38.8

36.0

33.2

27.5

25.4

23.4

22.1

21.3

19.1

16.9

14.8

12.6

10.3

 

Delta T

35.8

33.9

31.9

29.8

28.5

27.6

25.6

23.6

19.6

18.1

16.7

15.7

15.1

13.6

12.0

10.5

9.0

7.3

 

KW

3.58

3.52

3.45

3.38

3.34

3.31

3.25

3.18

2.31

2.27

2.23

2.20

2.18

2.14

2.09

2.05

2.01

1.96

 

AMPS

17.6

16.5

15.6

14.8

14.3

14.1

13.4

12.8

12.3

11.9

11.4

11.2

11.1

10.6

10.0

9.6

9.0

8.3

 

COP

4.11

3.96

3.80

3.62

3.50

3.42

3.24

3.05

3.48

3.27

3.07

2.94

2.85

2.61

2.36

2.11

1.84

1.54

 

EER

14.0

13.5

13.0

12.4

12.0

11.7

11.1

10.4

11.9

11.2

10.5

10.0

9.7

8.9

8.1

7.2

6.3

5.3

 

HI PR

323

310

298

285

278

273

262

252

241

230

221

216

212

204

196

188

181

175

 

LO PR

141

131

122

112

106

102

94

84

75

67

59

55

53

45

39

33

29

22

 

 

Above information is for nominal CFM and

70 degree indoor dry bulb.

Instantaneous capacity listed.

 

 

 

 

 

 

 

PERFORMANCE TEST

All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets:

If conditions vary from this, results will change as follows:

1.As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low and high side pressures and power will not change.

2.As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will occur in low and high side pressures and power.

A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown. A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.

A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.

A properly operating unit should be within plus or minus 3 Amps of the typical value shown.

25

Page 25
Image 25