PACKAGE HEAT PUMP SPECIFICATIONS GPH13[24-36]M41AB

 

 

GPH1324M41*

GPH1330M41*

GPH1336M41*

 

 

 

 

 

COOLING

COOLING CAPACITY, BTUH

24,000

29,000

34600

CAPACITY

SEER / EER

13/11

13/10.8

13/10.9

 

 

 

 

 

HEATING

BTU/h (47°)

23000

28800

34200

RATING

BTU/h (17°)

12600

17000

19000

 

HSPF

7.7

7.7

7.7

UNIT

VOLTAGE (NAMEPLATE)

208/230-60-1

208/230-60-1

208/230-60-1

ELECTRICAL

AMPS

15.8

19.0

21.3

SPECIFICATION

MIN CIRCUIT AMPACITY

19.0

23.0

25.4

 

MAX OVERCURRENT PROTECTION(1 )

30

35

40

COMPRESSOR

TYPE

SCROLL

SCROLL

SCROLL

 

RATED LOAD AMPS

12.8

16.0

16.7

 

LOCKED ROTOR AMPS

58.3

77

79

 

 

 

 

 

CONDENSER

HORSEPOWER

1/4

1/4

1/4

FAN MOTOR

RPM

830

830

830

 

FULL LOAD AMPS

1.5

1.5

1.5

 

LOCKED ROTOR AMPS

3

3

3

CONDENSER FAN

BLADE DIAMETER (INCHES)

22/3

22/3

22/4

NUMBER OF BLADES

 

 

 

 

 

 

 

 

 

CONDENSER

FACE AREA (SQ. FT.)

17.02

17.02

16.83

COIL

NUMBER OF ROWS

1

1

1

 

FINS PER INCH

24

24

22

 

 

 

 

 

EVAPORATOR

HORSEPOWER - NUMBER OF SPEEDS

1/4 - 3

1/3 - 3

1/3 - 3

BLOWER

FULL LOAD AMPS

1.5

1.5

3.06

MOTOR

LOCKED ROTOR AMPS

2.13

3.2

4.1

 

MOTOR SPEED TAP - COOLING X-13

High

High

High

 

RPM

952

869

910

 

 

 

 

 

EVAPORATOR

DIAMETER X WIDTH (INCHES)

10 x 9

10 x 9

10 x 9

BLOWER

RATED SCFM COOLING

825

1050

1150

 

MAX EXTERNAL STATIC PRESS ("w.c.)

0.5

0.5

0.5

 

 

 

 

 

EVAPORATOR

FACE AREA (SQ. FT.)

4.52

4.52

4.52

COIL

NUMBER OF ROWS

4

4

4

 

FINS PER INCH

16

16

14

 

 

 

 

 

GENERAL

FILTER SIZE *

25 x 25 x 1

25 x 25 x 1

25 x 25 x 1

INFORMATION

DRAIN SIZE (INCHES)

3/4"

3/4"

3/4"

 

EXPANSION DEVICE (ID/OD)

0.057/0.045

0.070/0.055

0.071/0.057

 

REFRIGERANT CHARGE R410A (OZS.)

110

115

135

 

POWER SUPPLY

3/4, 1, 1-1/4

3/4, 1, 1-1/4

3/4, 1, 1-1/4

 

CONDUIT KNOCKOUT SIZE (INCHES)

 

 

 

 

 

LOW VOLTAGE

1/2

1/2

1/2

 

CONDUIT KNOCKOUT SIZE (INCHES)

 

 

 

 

 

LO PRESSURE SWITCH

 

 

 

 

OPENS / CLOSES PSIG

22 / 50

22 / 50

22 / 50

 

HI PRESSURE SWITCH - OPENS PSIG

 

 

 

 

OPENS / CLOSES PSIG

660 / 420

660 / 420

660 / 420

 

SHIPPING WEIGHT (LBS.)

405

410

435

 

OPERATING WEIGHT (LBS.)

395

400

425

 

 

 

 

 

(1)Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted. * Calculated external filter size based on air velocity of 300 ft/min.

Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

Unit specifications are subject to change without notice. ALWAYS refer to the units serial plate for the most up-to-date general and electrical information. IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers

in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters.

8

Page 8
Image 8
Goodman Mfg RT6332013r1 service manual PACKAGE HEAT PUMP SPECIFICATIONS GPH1324-36M41AB