Goodman Mfg SS-GPH13MC warranty Airflow Data, Product Specifications

Models: SS-GPH13MC

1 16
Download 16 pages 7.88 Kb
Page 12
Image 12
Airflow Data

Product Specifications

Airflow Data

Model

Speed

Volts

 

 

 

 

E.S.P (In. of H₂O)

 

 

 

 

 

 

 

 

 

 

 

 

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

230

CFM

1122

1078

1032

972

915

804

687

558

 

 

 

 

 

 

 

 

 

 

 

Watts

338

330

321

310

300

283

264

250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GPH13

Med

230

CFM

1387

1331

1264

1209

1119

1041

935

748

 

 

 

 

 

 

 

 

 

36M43*

Watts

456

440

428

412

399

382

363

330

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

230

CFM

1521

1454

1388

1311

1230

1144

1055

939

 

 

 

 

 

 

 

 

 

 

 

Watts

534

521

510

490

477

461

442

420

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1 (G)

230

CFM

1,440

1,395

1,360

1,310

1,265

1,235

1,190

1,130

 

 

 

 

 

 

 

 

 

 

 

Watts

275

285

295

315

325

335

345

355

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GPH13

T2 / T3

230

CFM

1,795

1,765

1,715

1,695

1,650

1,600

1,500

1,375

 

 

 

 

 

 

 

 

 

48M43*

(W2)

Watts

475

490

505

520

530

535

510

475

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T4 / T5 (Y)

230

CFM

1,860

1,820

1,785

1,745

1,700

1,625

1,515

1,395

 

 

 

 

 

 

 

 

 

 

 

Watts

515

530

545

565

570

550

535

485

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1 (G)

230

CFM

1,755

1,720

1,685

1,645

1,615

1,570

1,530

1,465

 

 

 

 

 

 

 

 

 

 

 

Watts

420

435

455

460

475

490

500

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GPH13

T2 / T3

230

CFM

1,850

1,820

1,775

1,735

1,705

1,675

1,610

1,495

 

 

 

 

 

 

 

 

 

60M43*

(W2)

Watts

480

500

515

525

535

555

545

520

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T4 / T5 (Y)

230

CFM

2,180

2,125

2,050

1,975

1,875

1,800

1,655

1,530

 

 

 

 

 

 

 

 

 

 

 

Watts

770

755

725

700

675

640

575

540

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

Data shown is dry coil. Wet coil pressure drop is approximately 0.1" H₂O, for two-row indoor coil; 0.2” H₂O, for three-row indoor coil; and 0.3” H₂O, for four- row indoor coil.

Data shown does not include filter pressure drop, approx. 0.08” H2O.

ALL MODELS SHOULD RUN NO LESS THAN 350 CFM/TON. USE HIGHER SPEED TAP OR NEXT SIZE LARGER BLOWER ASM. See Repair Parts list.

Reduce airflow by 2% for 208-volt operation.

12

www.goodmanmfg.com

SS-GPH13MC

Page 12
Image 12
Goodman Mfg SS-GPH13MC warranty Airflow Data, Product Specifications