Product Specifications

Heat Kit Electrical Data (Blower Only, Heat Mode)

Model & Heat Kit Usage

 

Circuit #1

Actual kW / BTU@ 240V

 

 

 

MCA¹

MOD²

 

 

 

 

 

 

 

GPH1336M43**

3.06

/ 3.06

--

--

 

 

 

 

 

HKR3-15B

39

/ 45

60 / 60

15.0 / 51,000

 

 

 

 

 

GPH1348M43**

5.8

/ 5.8

--

--

 

 

 

 

 

HKR3-15B

39

/ 45

60 / 60

15.0 / 51,000

 

 

 

 

 

HKR3-20B

51

/ 55

60 / 60

19.5 / 66,500

 

 

 

 

 

GPH1360M43**

7.6

/ 7.6

--

--

 

 

 

 

 

HKR3-15B

39

/ 45

60 / 60

15.0 / 51,000

 

 

 

 

 

HKR3-20B

51

/ 55

60 / 60

19.5 / 66,500

 

 

 

 

 

¹Minimum Circuit Ampacity @ 208 / 240 V

²Maximum Overcurrent Protection device @ 208 / 240 V

* Revision level that may or may not be designated

C Circuit Breaker option

SS-GPH13MC

www.goodmanmfg.com