Goodman Mfg SS-GPH13MC warranty Product Specifications

Models: SS-GPH13MC

1 16
Download 16 pages 7.88 Kb
Page 3
Image 3
Specifications

Product Specifications

Specifications

GPH13

36M43**

GPH13

48M43**

GPH13

60M43**

Cooling Capacity

Total BTU/h

Sensible BTU/h

SEER / EER

Decibels

AHRI #s

34,000

48,000

57,500

24,140

36,800

40,800

13/10.8

13/11.5

13/11

80

80

80

4385123

4385128

4385131

 

 

 

Heating Capacity

BTU/h (47°F)

COP (47°F)

BTU/h (17°F)

COP (17°F)

HSPF

33,800

46,500

57,000

3.4

3.7

3.4

19,200

27,000

31,200

2.2

2.3

2.2

7.7

8.0

8.0

 

 

 

Evaporator Motor

Type

DD

EEM

EEM

 

 

 

 

Wheel (DxW)

10 x 9

10 x 9

10 x 9

 

 

 

 

Nominal Cooling CFM

1,050

1,720

1,800

 

 

 

 

Indoor Blower FLA / LRA

3.06 / 4.1

5.8 / --

7.6 / --

 

 

 

 

No. of Speeds

3

5

5

 

 

 

 

Horsepower - RPM

⅓ - 910

¾ - 1,050

1 - 1,050

 

 

 

 

Evaporator Coil

 

 

 

 

 

 

 

Face Area (ft²)

4.52

6.17

6.17

 

 

 

 

Rows Deep/ Fins per Inch

4 / 14

4 / 14

4 / 14

 

 

 

 

Drain Size (NPT)

¾"

¾"

¾"

 

 

 

 

Refrigerant Charge (oz)

141

205

220

 

 

 

 

Condenser Fan / Coil

 

 

 

 

 

 

 

Horsepower - RPM

¼ - 830

¼ - 1,075

¼ - 1,075

 

 

 

 

Oudoor Fan FLA / LRA

1.5 / 3.0

1.4 / 2.9

1.4 / 2.9

 

 

 

 

Fan Diameter / # Fan Blades

22/4

22/3

22/3

 

 

 

 

Face Area (ft²)

16.83

19.24

21.04

 

 

 

 

Rows Deep/Fins per Inch

1 / 22

2 / 16

2 / 16

 

 

 

 

Compressor

 

 

 

 

 

 

 

Quantity / Type

1 / Scroll

1 / Scroll

1 / Scroll

 

 

 

 

Stage

Single

Single

Single

 

 

 

 

Compressor RLA/LRA

10.4 / 73

13.7 / 83.1

16.0 / 110

 

 

 

 

Electrical Data

 

 

 

 

 

 

 

Voltage/ Phase/ Hz

208-230/3/60

208-230/3/60

208-230/3/60

 

 

 

 

Total Unit Amps

15.0

21.0

25.0

 

 

 

 

Min. Circuit Ampacity¹

17.6

24.3

29.0

 

 

 

 

Max. Overcurrent Protection²

25 amps

35 amps

45 amps

 

 

 

 

Ship/ Operating Weight (lbs)

419

531

542

 

 

 

 

¹Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes. ² May use fuses or HACR-type circuit breakers of the same size as noted.

Note: Always check the S&R plate for electrical data on the unit being installed.

SS-GPH13MC

www.goodmanmfg.com

3

Page 3
Image 3
Goodman Mfg SS-GPH13MC warranty Product Specifications