Goodman Mfg SS-GSX13 dimensions Specifications

Models: SS-GSX13

1 40
Download 40 pages 59.18 Kb
Page 3
Image 3

Product Specifications

Specifications

 

GSX13

GSX13

GSX13

GSX13

GSX13

GSX13

GSX13

GSX13

GSX13

 

0181E*

0241D*

0301B*

0361C*

0361E*

0421B*

0481B*

0601B*

0611A*

 

 

 

 

 

 

 

 

 

 

Capacities

 

 

 

 

 

 

 

 

 

Nominal Cooling (BTU/h)

18,000

24,000

30,000

36,000

36,000

42,000

48,000

60,000

60,000

SEER / EER

13 / 11

13 / 11

13 / 11

13 / 11

13 / 11

13 / 11

13 / 11

13 / 11

13/11

Decibels

75

75

73

74

74

75

76

77

72

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

RLA

6.7

13.5

12.8

14.1

14.1

17.9

19.9

25.0

26.4

LRA

41

58.3

64

77

77

112

109

134

134

 

 

 

 

 

 

 

 

 

 

Condenser Fan Motor

 

 

 

 

 

 

 

 

 

Horsepower

1/8

1/8

1/8

1/6

1/4

1/4

1/4

1/4

1/4

FLA

0.7

0.7

0.7

1.1

1.5

1.5

1.5

1.5

1.5

 

 

 

 

 

 

 

 

 

 

Refrigeration System

 

 

 

 

 

 

 

 

 

Refrigerant Line Size ¹

 

 

 

 

 

 

 

 

 

Liquid Line Size (“O.D.)

⅜"

⅜"

⅜"

⅜"

⅜"

⅜"

⅜"

⅜"

⅜"

Suction Line Size (“O.D.)

¾"

¾"

¾"

⅞"

⅞"

1⅛"

1⅛"

1⅛"

⅞"

Refrigerant Connection Size

 

 

 

 

 

 

 

 

 

Liquid Valve Size (“O.D.)

⅜"

⅜"

⅜"

⅜"

⅜"

⅜"

⅜"

⅜"

⅜"

Suction Valve Size (“O.D.) ⁴ ⁵

¾"

¾"

¾"

¾" ⁴

¾" ⁴

⅞" ⁵

⅞" ⁵

⅞" ⁵

¾"

Valve Type

Sweat

Sweat

Sweat

Sweat

Sweat

Sweat

Sweat

Sweat

Sweat

Refrigerant Charge

73

76

78

89

75

90

104

111

130

Shipped with Orifice Size

0.051

0.057

0.061

0.070

0.070

0.076

0.080

0.086

0.086

 

 

 

 

 

 

 

 

 

 

Electrical Data

 

 

 

 

 

 

 

 

 

Voltage

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

208/230

Minimum Circuit Ampacity ²

9.1

17.6

16.7

18.7

19.1

23.9

26.3

32.8

34.5

Max. Overcurrent Protection ³

15 amps

30 amps

25 amps

30 amps

30 amps

40 amps

45 amps

50 amps

60 amps

Min / Max Volts

197/253

197/253

197/253

197/253

197/253

197/253

197/253

197/253

197/253

Electrical Conduit Size

½" or ¾"

½" or ¾"

½" or ¾"

½" or ¾"

½" or ¾"

½" or ¾"

½" or ¾"

½" or ¾"

½" or ¾"

 

 

 

 

 

 

 

 

 

 

Equipment Weight (lbs)

106

113

142

139

139

188

191

207

284

Ship Weight (lbs)

120

130

159

157

157

206

209

225

301

 

 

 

 

 

 

 

 

 

 

¹ Line sizes denoted for 25’ line sets, tested and rated in accordance with AHRI Standard 210/240. For other line-set lengths or sizes, refer to the installation & Operating instructions and/or the long line-set guidelines.

²Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes ³ Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.

⁴ Installer will need to supply ¾” to ⅞” adapters for suction line connections. ⁵ Installer will need to supply ⅞” to 1⅛” adapters for suction line connections.

Notes

Always check the S&R plate for electrical data on the unit being installed.

Unit is charged with refrigerant for 15’ of ⅜” liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.

SS-GSX13

www.goodmanmfg.com

3

Page 3
Image 3
Goodman Mfg SS-GSX13 dimensions Specifications