HEATING PERFORMANCE DATA |
|
|
|
| ||||||||||||||
|
|
|
|
|
| EXPANDED PERFORMANCE DATA |
|
|
|
|
| |||||||
MODEL: |
|
|
|
|
|
|
| HEATING OPERATION | ||||||||||
|
|
|
|
|
|
| Outdoor Ambient Temperature |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 65 | 60 | 55 | 50 | 47 | 45 | 40 | 35 | 30 | 25 | 20 | 17 | 15 | 10 | 5 | 0 | ||
MBh | 54.1 | 51.2 | 48.2 | 45.0 | 43.0 | 41.7 | 38.7 | 35.7 | 33.6 | 31.1 | 28.6 | 27.0 | 26.0 | 23.3 | 20.7 | 18.0 | 15.4 | 12.6 |
Delta T | 30.6 | 29.0 | 27.3 | 25.5 | 24.4 | 23.6 | 21.9 | 20.2 | 19.1 | 17.6 | 16.2 | 15.3 | 14.7 | 13.2 | 11.7 | 10.2 | 8.7 | 7.1 |
KW | 4.11 | 4.04 | 3.96 | 3.88 | 3.84 | 3.81 | 3.73 | 3.65 | 4.07 | 3.98 | 3.89 | 3.84 | 3.80 | 3.71 | 3.62 | 3.53 | 3.44 | 3.35 |
AMPS | 8.6 | 8.1 | 7.7 | 7.3 | 7.1 | 7.0 | 6.7 | 6.4 | 6.2 | 6.0 | 5.8 | 5.7 | 5.6 | 5.4 | 5.2 | 5.0 | 4.7 | 4.4 |
COP | 3.85 | 3.71 | 3.56 | 3.39 | 3.28 | 3.20 | 3.03 | 2.86 | 2.42 | 2.28 | 2.15 | 2.06 | 2.00 | 1.84 | 1.67 | 1.49 | 1.31 | 1.10 |
EER | 13.1 | 12.7 | 12.2 | 11.6 | 11.2 | 10.9 | 10.4 | 9.8 | 8.3 | 7.8 | 7.3 | 7.0 | 6.8 | 6.3 | 5.7 | 5.1 | 4.5 | 3.8 |
HI PR | 252 | 242 | 232 | 222 | 217 | 213 | 205 | 196 | 188 | 180 | 173 | 168 | 165 | 159 | 153 | 147 | 141 | 136 |
LO PR | 76 | 71 | 66 | 61 | 57 | 55 | 51 | 45 | 41 | 36 | 32 | 30 | 29 | 24 | 21 | 18 | 15 | 12 |
MODEL: |
|
|
|
|
|
|
| HEATING OPERATION | ||||||||||
|
|
|
|
|
|
| Outdoor Ambient Temperature |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 65 | 60 | 55 | 50 | 47 | 45 | 40 | 35 | 30 | 25 | 20 | 17 | 15 | 10 | 5 | 0 | ||
MBh | 69.8 | 66.0 | 62.2 | 58.1 | 55.5 | 53.8 | 50.0 | 46.1 | 43.6 | 40.3 | 37.1 | 35.0 | 33.7 | 30.2 | 26.8 | 23.4 | 20.0 | 16.3 |
Delta T | 34.3 | 32.5 | 30.6 | 28.6 | 27.3 | 26.4 | 24.6 | 22.7 | 21.4 | 19.8 | 18.2 | 17.2 | 16.6 | 14.9 | 13.2 | 11.5 | 9.8 | 8.0 |
KW | 5.25 | 5.15 | 5.05 | 4.95 | 4.89 | 4.85 | 4.75 | 4.65 | 5.20 | 5.08 | 4.96 | 4.89 | 4.84 | 4.72 | 4.61 | 4.49 | 4.37 | 4.25 |
AMPS | 10.5 | 9.8 | 9.3 | 8.9 | 8.6 | 8.5 | 8.1 | 7.7 | 7.5 | 7.2 | 7.0 | 6.8 | 6.8 | 6.5 | 6.2 | 5.9 | 5.6 | 5.2 |
COP | 3.89 | 3.75 | 3.60 | 3.44 | 3.32 | 3.25 | 3.08 | 2.90 | 2.46 | 2.32 | 2.19 | 2.09 | 2.04 | 1.87 | 1.70 | 1.52 | 1.34 | 1.12 |
EER | 13.3 | 12.8 | 12.3 | 11.7 | 11.3 | 11.1 | 10.5 | 9.9 | 8.4 | 7.9 | 7.5 | 7.2 | 7.0 | 6.4 | 5.8 | 5.2 | 4.6 | 3.8 |
HI PR | 270 | 258 | 248 | 238 | 232 | 228 | 219 | 210 | 201 | 192 | 184 | 180 | 177 | 170 | 164 | 157 | 151 | 146 |
LO PR | 77 | 71 | 67 | 61 | 58 | 56 | 51 | 46 | 41 | 37 | 32 | 30 | 29 | 25 | 21 | 18 | 16 | 12 |
*Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temperature |
|
|
|
|
|
|
|
|
| |||||||||
MODEL: GSH130483B*, 484A* / AR*F496016B |
|
|
|
|
|
|
|
| HEATING OPERATION | |||||||||
|
|
|
|
|
|
| Outdoor Ambient Temperature |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 65 | 60 | 55 | 50 | 47 | 45 | 40 | 35 | 30 | 25 | 20 | 17 | 15 | 10 | 5 | 0 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
MBh | 60.1 | 56.9 | 53.6 | 50.1 | 47.8 | 46.3 | 43.0 | 39.7 | 35.9 | 33.1 | 30.5 | 28.8 | 27.7 | 24.9 | 22.1 | 19.2 | 16.4 | 13.5 |
Delta T | 34.8 | 32.9 | 31.0 | 29.0 | 27.7 | 26.8 | 24.9 | 23.0 | 20.8 | 19.2 | 17.7 | 16.7 | 16.1 | 14.4 | 12.8 | 11.1 | 9.5 | 7.8 |
KW | 4.54 | 4.43 | 4.33 | 4.23 | 4.17 | 4.12 | 4.02 | 3.92 | 3.55 | 3.45 | 3.35 | 3.30 | 3.26 | 3.16 | 3.07 | 2.97 | 2.87 | 2.78 |
AMPS | 13.6 | 12.6 | 11.8 | 11.2 | 10.8 | 10.6 | 10.0 | 9.6 | 9.2 | 8.8 | 8.4 | 8.2 | 8.1 | 7.7 | 7.3 | 6.9 | 6.4 | 5.8 |
COP | 3.88 | 3.76 | 3.62 | 3.47 | 3.36 | 3.29 | 3.13 | 2.97 | 2.96 | 2.81 | 2.66 | 2.56 | 2.49 | 2.30 | 2.11 | 1.89 | 1.67 | 1.42 |
EER | 13.2 | 12.8 | 12.4 | 11.9 | 11.5 | 11.2 | 10.7 | 10.1 | 10.1 | 9.6 | 9.1 | 8.7 | 8.5 | 7.9 | 7.2 | 6.5 | 5.7 | 4.8 |
HI PR | 266 | 255 | 245 | 234 | 229 | 224 | 216 | 207 | 198 | 189 | 182 | 178 | 174 | 168 | 161 | 155 | 149 | 144 |
LO PR | 77 | 71 | 67 | 61 | 58 | 56 | 51 | 46 | 41 | 37 | 32 | 30 | 29 | 24 | 21 | 18 | 16 | 12 |
High pressure is measured at the suction service valve ( the larger valve).
Low pressure is measured at the gauge port connection.
Calculations are based on nominal CFM and 70 °F indoor dry bulb.
PERFORMANCE TEST
AMPS = Outdoor unit amps (comp.+fan) KW = Total system power
All data based upon listed indoor dry bulb temperature. .00 inches exter- nal static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets:
If conditions vary from this, results will change as follows:
1.As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low and high side pressures and power will not change.
2.As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will occur in low and
high side pressures and power.
24
A properly operating unit should be within plus or minus 2 degrees of the subcooling value shown in the Heat Pump Specifications.
A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.
A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.
A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.
A properly operating unit should be within plus or minus 3 Amps of the typical value shown.