Goodmans RT6212008x5 service manual Heat Pump Specifications, GSH13036-603* GSH13048-604

Models: GSH 13 SEER - 3 Phase Split System Heat Pump RT6212008x5

1 26
Download 26 pages 25.74 Kb
Page 6
Image 6

HEAT PUMP SPECIFICATIONS

GSH130[36-60]3* GSH130[48-60]4*

 

GSH130363AE

GSH130363AF

GSH130483AE

GSH130603AC

GSH130484AC

GSH130604AC

 

 

 

 

 

 

 

Cooling Capacity, BTUH

35,000

31,400

45,000

55,500

45,000

55,500

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

R.L. Amps

9.0

9.9

12.4

17.3

5.8

6.7

L.R. Amps

65.5

73.0

88.0

123.0

44.0

49.5

Loss of Charge Pressure Switch

 

 

 

 

 

 

Open / Close

7 PSIG/25 PSIG

7 PSIG/25 PSIG

7 PSIG/25 PSIG

7 PSIG/25 PSIG

7 PSIG/25 PSIG

7 PSIG/25 PSIG

 

 

 

 

 

 

 

Condenser Fan Motor

 

 

 

 

 

 

Horsepower

1/4

1/4

1/4

1/6

1/4

1/6

F.L. Amps

1.5

1.5

1.5

1.1

0.8

0.6

 

 

 

 

 

 

 

Liquid Line, Inches O.D.

3/8"

3/8"

3/8"

3/8"

3/8"

3/8"

Suction Line, Inches O.D.

7/8"

7/8"

7/8"

7/8"

7/8"

7/8"

Refrigerant Charge

188

188

223

233

223

233

 

 

 

 

 

 

 

Power Supply

208/230-60-3

208/230-60-3

208/230-60-3

208/230-60-3

460-60-3

460-60-3

Minimum Circuit Ampacity(1)

12.7

13.9

17.1

22.7

8.0

9.0

Maximum Overcurrent Device(2)

20

20

20

40

15

15

Electrical Conduit Size

 

 

 

 

 

 

Power Supply (Inches)

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

1/2 or 3/4

Approximate Shipping Weight

207

207

225

266

225

266

 

 

 

 

 

 

 

(1)Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

(2)Maximum Overcurrent Protection: Must use fuses or HACR-type Circuit Breakers of the same size as noted.

NOTES:

*Always check the S&R plate for electrical data on the unit being installed.

*Installer will need to supply 7/8" to 1 1/8" adapters for suction line connections.

*Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge Procedure.

*Installation of these units that require a TXV Kit to be installed on the indoor coil: PLEASE NOTE: THE SPECIFIED TXV IS DETERMINED BY THE OUTDOOR UNIT NOT THE INDOOR COIL

6

Page 6
Image 6
Goodmans RT6212008x5, GSH 13 SEER - 3 Phase Split System Heat Pump Heat Pump Specifications, GSH13036-603* GSH13048-604