GOSSEN METRAWATT GMBH 7
Following, the master may only become active again, when
it receives a reply telegram from the addressed equipment and the specified wait time after a reply telegram (t aw) has elapsed, or
the maximum specified response delay time (tav) has elapsed.
Within a telegram, pauses of limited duration (tzv = character delay time) may occur between 2 character transmissions.
1.5 Time action
Ready to send/receive after turn-on tber approx. 5 s
Character delay time (R2600 transmitter) tzvs <3ms
Character delay time (master) tzvm < 500ms
Response delay time (R2600 transmitter) 10ms < tav <100ms
Wait time after R2600 response (master) t aw > 10 ms
Time
Master
sends
Equipment
responds
tber
approx. 5s
tav
10 ...
100ms
tzvs
< 3ms
Master
sends
taw
> 10ms
tzvm
< 500ms