Pressure Mode Examples
•Runaway Control: The user may choose to set the maximum flow to Alarm. If the flow rate exceeds the maximum entered on Setup Screen 3, an Alarm symbol will show on screen and the pump will shut down.
•Detect a Plugged Filter or Pipe: The user may choose to set the minimum flow to Deviation. If the flow rate drops below the minimum entered on Setup Screen 3, a Deviation symbol will show on screen to warn the user that action should be taken. The pump continues to run.
Setup Screens
Flow Mode Examples
•Runaway Control: The user may choose to set the minimum pressure to Alarm. If a hose bursts, the pump will not change speed, but the back pressure will fall. When the pressure falls below the minimum entered on Setup Screen 2, an Alarm symbol will show on screen and the pump will shut down.
•Protect Connected Equipment: The user may choose to set the maximum pressure to Limit to prevent the connected equipment from excessive pressure.
•Detect a Plugged Filter or Pipe: The user may choose to set the maximum pressure to Deviation. When the pressure exceeds the maximum entered on Setup Screen 2, a Deviation symbol will show on screen to warn the user that action should be taken. The pump continues to run.