Service Schedule

Maintenance

Level 1

 

Level 2

 

Level 3

 

Level 4

 

Level5

 

Tasks

Recom-

Task

Required

Task

Required

Task

 

Task

Required

Task

 

mended

Comp.

to be done

Comp.

to be done

Comp.

Required

Comp.

to be done

Comp.

 

to be done

(Date-

3 months/

(Date-

Semi-

(Date-

to be done

(Date-

Bi-

(Date-

 

monthly/

Initials)

Break-in

Initials)

annually/

Initials)

Annually/

Initials)

annually/

Initials)

 

10 hrs.

 

30 hrs.

 

50 hrs.

 

100 hrs.

 

250 hrs.

 

10.Check the engine accessory drive belts and fan coupling device if equipped for

correct tension, wear, weather cracking, and damage. Replace as necessary.

11.Check the engine valve clearance/ lash. Adjust as necessary.**

12.Visually inspect the unit looking for leaks, wear or damage, loose connections or components, and corrosion. Correct as necessary.

13.Test the engine and transfer switch safety devices. Correct and/or adjust as necessary.

14.Initiate an automatic start and transfer of the unit to site load and exercise

it for at least 1 hour looking for leaks, loose connections or components, and abnormal operating conditions. Correct as necessary.

15.Replace the engine accessory drive belts.

16.Check gearbox

oil level (if equipped).

17. Change gearbox oil (if equipped).

** Not required for engines equipped with hydraulic lifters. See the "Specification" section for lifter type.

11-3