Grandstream Networks 005261-0 owner manual Troubleshooting Guide, Problem, Cause, Correction

Models: 005261-0

1 64
Download 64 pages 37.86 Kb
Page 24
Image 24
Stationary Emergency Generator

Stationary Emergency Generator

Troubleshooting

TROUBLESHOOTING GUIDE

PROBLEM

CAUSE

CORRECTION

Engine won’t crank.

1.

15 amp fuse blown.

1.

Replace fuse.

 

2.

Loose or corroded or defective

2.

Tighten, clean or replace

 

 

battery cables.

 

battery cables as necessary.

 

3.

Defective starter contactor.

3.

Replace contactor.*

 

4.

Defective starter motor.

4.

Replace starter motor.*

 

5.

Dead or Defective Battery.

5.

Remove, change or replace battery.

 

6.

5 amp fuse blown.

6.

Replace fuse.*

 

 

 

 

 

Engine cranks but won't start

1.

Out of fuel.

1.

Replenish fuel.

 

2.

Fuel solenoid (FS) is defective

2.

Replace solenoid.*

 

3.

Open Wire #14A from Engine Control

3.

Reconnect wire.

 

 

circuit board.

 

 

 

4.

Spark plugs defective.

4.

Clean, regap or replace plugs.

 

5.

Door on tank not closed.

5.

Close door on tank.

 

 

 

 

 

Engine starts hard, runs rough.

1.

Flame arrestor (air cleaner) plugged or

1.

Clean or replace as needed.

 

 

damaged.

 

 

 

2.

Plugged fuel line.

2.

Unclog fuel line.

 

3.

Defective spark plugs.

3.

Clean, regap or replace plugs.

 

4.

Fuel pressure incorrect.

4.

Confirm fuel pressure to regulator is as

 

 

 

 

recommended in SPECIFICATIONS.

 

 

 

 

 

Engine starts then shuts down.

1.

Engine oil level is low.

1.

Check oil and add oil as needed.

 

2.

Engine is overheated.

2.

Check cooling system for leaks.

 

3.

Defective Low Oil Pressure Switch

3.

Replace switch.*

 

4.

Defective Coolant Temperature Switch

4.

Replace switch.*

 

5.

Defective Control Module circuit board.

5.

Replace board.*

 

6.

Coolant Level is Low.

6.

Repair leak - Add coolant.

 

7.

Defective Low Coolant Level Switch

7.

Replace Switch.*

 

 

 

 

 

AUTO/OFF/MANUAL Switch at OFF,

1.

Defective AUTO/OFF/MANUAL switch

1.

Replace switch.*

engine continues to run

2.

Open/disconnected wire #15A between

2.

Reconnect/close wire.

 

 

AUTO/OFF/MANUAL switch and Control

 

 

 

 

Module circuit board.

 

 

 

3.

Defective Control Module circuit board

3.

Replace board.*

 

 

 

 

 

No AC output from generator.

1.

Check main line circuit breaker.

1.

Reset to ON or CLOSED.

 

2.

Check circuit breaker & fuses.

2.

Reset and replace, if necessary.

 

3.

Transfer switch set to NORMAL position

3.

Set to GENERATOR position.

 

4.

Generator internal failure.

4.

*

 

5.

Thermal circuit breaker open.

5.

Auto-reset - Wait 5 min. and

 

 

 

 

attempt restart.

*Contact the nearest Authorized Dealer for assistance.

12-1

10/08 A .Rev Trblsht001

Page 24
Image 24
Grandstream Networks 005261-0 owner manual Troubleshooting Guide, Problem, Cause, Correction