Certifications & Listings
Seismic Certification
The International Building Code (IBC) has been adopted at the state and level throughout the United States. With the adoption of this code, comes introduction of standards intended to improve the performance and design
QEI-I/II and QEID
•Meet the 2006 IBC, 2009 IBC
•California OSHPD requirements (horizontal mount only) OSP
•Shake table tested at an independent test facility in accordance with
•All equipment certified to worst case scenario seismic conditions
- | Importance factor of 1.5 (IP = 1.5) | - | Occupancy Categories (I - IV) |
- | Site Classes (A - F) | - | Seismic Design Categories (A - F) |
Structural Finite Element Analysis
Seismic Design Category F
Consult your Greenheck representative or visit greenheck.com/seismic for more details.
UL 705 Power Ventilator
Motors are available as either IEC (IP55) or NEMA (TEAO or ODP) designs. IEC design motors are adjustable speed drive (ASD) compatible, have class F insulation and are capable of
a 1.0 service factor, while 60 Hz power have 1.15 service factor. Design and construction options for motors include increased thermal insulation, overload protection and extended motor leads.
UL Emergency Smoke Evacuation
UL/cUL File MH17511
UL/cUL Power Ventilators for Smoke Control Systems
| Operating | Time |
| ||
Model | Temperature | Duration |
| ||
| ºC | ºF | Hours | Comments | |
|
|
|
|
| |
QEID | 300 | 572 | 1 | Per British Spec 7346 | |
|
|
|
| ||
300 | 572 | 2 | |||
| |||||
|
|
|
|
| |
260 | 500 | 4 | Per Industrial Risk | ||
QEID | 260 | 500 | 5 | Insurers (North America) | |
|
|
|
|
|
Consult your Greenheck representative for time and temperature combinations other than those listed.
UL 762 Restaurant Exhaust
Inline grease exhaust fans are an excellent alternative for kitchen applications when roof or wall mounted ventilators are not practical. A
A Tough Package to Beat
The
10
Listed Power Ventilation for Restaurant Exhaust Appliances 13G3 Maximum Operating Temperature 400°F.
UL 762 is concerned with fans designed for removal of smoke and grease laden vapors with airstream temperatures up
to 400°F.
•Meets all UL 705 requirements
•UL/cUL File MH11745 UL/cUL Power Ventilators for Restaurant Exhaust Appliances
•Bolted access door
•Drain connection