Greenheck Fan Vektor-HS Plenum Drainage Piping / Trap Detail By Others, Electrical Connections

Models: Vektor-HS Vektor-H

1 12
Download 12 pages 14.2 Kb
Page 7
Image 7
Plenum Drainage Piping / Trap Detail (By Others)

Plenum Drainage Piping / Trap Detail (By Others)

Fan Drain

Plenum Drain

Connection

Connection

There is a location for a pipe connection on each tubular fan housing and bypass air plenum. Each drain may need to be connected to a drainage system to ensure proper disposal of any water or condensate that may occur.

t %SBJODPOOFDUJPOTBSFJODI/15

t *OTUBMMFEQJQJOHUPIBWFBEPXOXBSEBOHMFUPBMMPX for drainage

t 'JMMUSBQTUPSFDPNNFOEFEMFWFMCFGPSFTUBSUVQ

Note: A conservative method of trap design is to set N = total static pressure.

Positive Pressure Trap on Tubular Fan Housing

Connect

 

1.25 inch

 

minimum

this end

 

 

 

to fan drain.

 

 

 

 

N

H/2

H

H/2

FAN OFF

 

FAN ON

N = Negative fan pressure (inches W.C.)

H = N - (0.5 inches minimum)

for compatibility with the fan motor. In addition, the supply wiring must be properly fused and conform to local and national electrical codes. If the unit is supplied with a safety disconnect switch, ensure proper wiring to the fan motor. Be sure the disconnect is switched to the “OFF” position before connecting supply wires. If no disconnect is supplied, ensure the supply wire is not live before connection. Supply wires are then connected to the optional safety disconnect switch (if supplied) or motor.

Vektor-H Motor Disconnect and Isolation Damper Wiring Diagram

Disconnect is mounted to fan housing. Transformers are mounted to bypass air plenum with damper actuator motors. For systems that ship unassembled because of physical size, this connection at disconnect from transformers must be field-installed. Wires with conduit and fittings are provided pre-connected to transformers.

Single Phase Layout

 

 

LINE IN

 

 

 

 

 

 

 

 

 

Field Wiring

115/208/230/277 volt, single phase

 

 

 

 

 

 

 

 

 

Factory Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DISCONNECT

 

 

 

 

 

 

 

 

Disconnect is mounted to fan housing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

115/208/230/277 volt

 

 

 

 

 

 

 

 

Optional transformer and isolation damper, refer to CAPS file selection

Single phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230/277 volt, single phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transformers must be wired independent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOTOR

 

 

 

 

 

 

 

from VFD control.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24/115 volt, single phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

isolation damper actuator motor

115/208/230/277 volt

 

 

 

 

 

 

 

power open/spring close

 

 

 

 

 

 

 

 

 

 

 

Single phase

 

 

 

 

 

 

 

 

 

 

Three Phase Layout

LINE IN

 

 

Field Wiring

208/230/460/575 volt, three phase

 

 

 

 

 

 

Factory Wiring

 

 

Disconnect is mounted to fan housing

 

 

 

Negative Pressure Trap on Bypass Air Plenum

 

 

1.25 inch minimum

 

 

N

H

H/2

H/2

DISCONNECT

208/230/460/575 volt

Three phase

MOTOR

208/230/460/575 volt 60 cycle, three phase

Optional transformer and isolation damper, refer to CAPS file selection

TRANSFORMER

208/230/460/575 volt, single phase

Transformers must be wired independent

from VFD control.

24/115 volt, single phase isolation damper actuator motor power open/spring close

FAN OFF

FAN ON

N = Negative fan pressure (inches W.C.)

H = N - (0.5 inches minimum

Electrical Connections

NOTE

Refer to the Vektor-HS SAVVE controls Installation, Operation and Maintenance Manual for electrical wiring and connection information.

Before electrical connections are made, the supply voltage, phase and ampere capacity must be checked

Three Phase with

Variable Frequency Drives Layout

LINE IN

208/230/460/575 volt, three phaseField Wiring

Factory Wiring

VFD

supplied and wired

by others

 

Disconnect is mounted to fan housing

DISCONNECT

Optional transformer and isolation damper,

208/230/460/575 volt

refer to CAPS file selection

Three phase

 

 

TRANSFORMER (if required)

 

208/230/460/575 volt, single phase

 

Transformers must be wired independent

 

from VFD control.

MOTOR

24/115 volt, single phase

 

isolation damper actuator motor

 

power open/spring close

208/230/460/575 volt

 

60 cycle, three phase

 

Laboratory Exhaust System 7

®

Page 7
Image 7
Greenheck Fan Vektor-HS manual Plenum Drainage Piping / Trap Detail By Others, Electrical Connections