Plenum Drainage Piping / Trap Detail (By Others)
Fan Drain | Plenum Drain |
Connection | Connection |
There is a location for a pipe connection on each tubular fan housing and bypass air plenum. Each drain may need to be connected to a drainage system to ensure proper disposal of any water or condensate that may occur.
t %SBJODPOOFDUJPOTBSFJODI/15
t *OTUBMMFEQJQJOHUPIBWFBEPXOXBSEBOHMFUPBMMPX for drainage
t 'JMMUSBQTUPSFDPNNFOEFEMFWFMCFGPSFTUBSUVQ
Note: A conservative method of trap design is to set N = total static pressure.
Positive Pressure Trap on Tubular Fan Housing
Connect |
| 1.25 inch |
| minimum | |
this end |
| |
|
| |
to fan drain. |
|
|
|
| N |
H/2 | H | H/2 |
FAN OFF |
| FAN ON |
N = Negative fan pressure (inches W.C.)
H = N - (0.5 inches minimum)
for compatibility with the fan motor. In addition, the supply wiring must be properly fused and conform to local and national electrical codes. If the unit is supplied with a safety disconnect switch, ensure proper wiring to the fan motor. Be sure the disconnect is switched to the “OFF” position before connecting supply wires. If no disconnect is supplied, ensure the supply wire is not live before connection. Supply wires are then connected to the optional safety disconnect switch (if supplied) or motor.
Vektor-H Motor Disconnect and Isolation Damper Wiring Diagram
Disconnect is mounted to fan housing. Transformers are mounted to bypass air plenum with damper actuator motors. For systems that ship unassembled because of physical size, this connection at disconnect from transformers must be
Single Phase Layout
|
| LINE IN |
|
|
|
|
|
|
|
|
| Field Wiring | ||||||
115/208/230/277 volt, single phase |
|
|
|
|
|
|
|
|
| Factory Wiring | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
DISCONNECT |
|
|
|
|
|
|
|
| Disconnect is mounted to fan housing |
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
115/208/230/277 volt |
|
|
|
|
|
|
|
| Optional transformer and isolation damper, refer to CAPS file selection | |||||||||
Single phase |
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| TRANSFORMER | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 208/230/277 volt, single phase | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Transformers must be wired independent | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| MOTOR |
|
|
|
|
|
|
| from VFD control. | ||||||||
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 24/115 volt, single phase | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| isolation damper actuator motor | ||
115/208/230/277 volt |
|
|
|
|
|
|
| power open/spring close | ||||||||||
|
|
|
|
|
|
|
|
|
| |||||||||
| Single phase |
|
|
|
|
|
|
|
|
|
|
Three Phase Layout
LINE IN |
|
| Field Wiring | |
208/230/460/575 volt, three phase |
|
| ||
|
|
|
| Factory Wiring |
|
| Disconnect is mounted to fan housing |
| |
|
|
Negative Pressure Trap on Bypass Air Plenum
|
| 1.25 inch minimum |
|
| N |
H | H/2 | H/2 |
DISCONNECT
208/230/460/575 volt
Three phase
MOTOR
208/230/460/575 volt 60 cycle, three phase
Optional transformer and isolation damper, refer to CAPS file selection
TRANSFORMER
208/230/460/575 volt, single phase
Transformers must be wired independent
from VFD control.
24/115 volt, single phase isolation damper actuator motor power open/spring close
FAN OFF | FAN ON |
N = Negative fan pressure (inches W.C.)
H = N - (0.5 inches minimum
Electrical Connections
NOTE
Refer to the
Before electrical connections are made, the supply voltage, phase and ampere capacity must be checked
Three Phase with
Variable Frequency Drives Layout
LINE IN
208/230/460/575 volt, three phaseField Wiring
Factory Wiring
VFD
supplied and wired
by others
| Disconnect is mounted to fan housing | |
DISCONNECT | Optional transformer and isolation damper, | |
208/230/460/575 volt | ||
refer to CAPS file selection | ||
Three phase | ||
| ||
| TRANSFORMER (if required) | |
| 208/230/460/575 volt, single phase | |
| Transformers must be wired independent | |
| from VFD control. | |
MOTOR | 24/115 volt, single phase | |
| isolation damper actuator motor | |
| power open/spring close | |
208/230/460/575 volt |
| |
60 cycle, three phase |
|
Laboratory Exhaust System 7
®