2. Description and Operation of Dual Level Control System (continued):

B.Operation Water Level

1) Below both electrodes

Action

1)Both “HI” and “XL” electrode circuits open. Dual Level Control turns power on to fill valve and keeps power off to thermostat.

 

Fill Solenoid

Thermostat

 

Valve

OFF

2) Rises to low electrode above

ON

2) “XL” electrode circuit closes. Power to

above heater coils

thermostat turned on.

Power to fill valve

 

remains on.

 

3)Rises to high electrode

4)Falls below high electrode only

Fill Solenoid

Thermostat

Valve

 

ON ON

3)“HI” electrode circuit closes. Dual Level Control turns power off to fill valve and con- tinues power to thermostat.

Fill Solenoid

Thermostat

Valve

 

OFF ON

4)“HI” electrode circuit opens. “XL” circuit stays closed. After a few seconds delay, power to fill valve is turned on.

Fill Solenoid

Thermostat

Valve

 

ON ON

5) Falls below low electrode.

5) “XL” electrode circuit now opens. Power

(Same as condition no. 1)

to thermostat is turned off. Power to fill

valve remains on.

 

3.Quick Service Check of Dual Level Control System:

1)All wire secure and properly connected.

2)Clean the electrodes. Lime (mineral scale) build-up can interfere with the operation of any liquid level control system.

3)Check the common (ground) connection. A little looseness or dirt can cause erratic operation.

 

 