For buildings that are not well sealed (do not have tight fitting doors and windows) natural air infiltration may provide sufficient air required for combustion and ventilation. For buildings using tight construction (newer and renovated structures), the air supply shall be introduced from the outdoors, regardless of whether the space is confined or unconfined.

Combustion Air “Supply” Ducts

Air supply ducts shall be of galvanized steel or equivalent corrosion resistant material. A single air duct may not be substituted when required for upper and lower air openings. Horizontal upper combustion air ducts shall not slope downward toward the air inlet.

Louvers and Grills

Openings for air supply ducts must provide free unobstructed air movement. Louver and grill openings must be sized to ensure that the FREE OPEN AREA is never less than the area of the air duct.

LOCATION:

The location for top and bottom openings are as follows;

For American installations:The top opening shall commence within 12” (30 cm) of the top of space and the bottom opening shall commence within 12” (30 cm) of the bottom of the enclosure.

For Canadian installations:The top opening shall be located as close to the ceiling as practical but never lower than the relief opening of the lowest draft control device. The bottom opening shall be located neither more than 18 inches (450 mm), nor less than 6 inches (150 mm), above floor level.

Air Opening Requirements

(a)EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR FROM INSIDE THE BUILDING.

Two permanent openings (top and bottom) shall be provided connecting the

 

confined space (e.g., closet/small room) with the unconfined space. Each opening

 

shall have a free area of one square

inch per 1,000 BTU/hour(22 cm²/kW) input of

*

all appliances in the confined space, but not less than 100 square inches (645 cm²).

(b) BASEMENT INSTALLATION, EQUIPMENT LOCATED IN CONFINED

 

SPACES; ALL AIR FROM OUTDOORS.

 

 

 

Outside air inlets shall be a minimum of 12” (30 cm) above the grade (snow) line.

 

When supplying air directly from the outdoors:

 

 

 

For American installations: Two openings (top and bottom) shall be provided with

 

each opening having a minimum free area of one square inch per 4,000 BTU/hour

 

input (5.5 cm²/kW) of total input rating of all appliances in the confined space.

 

For Canadian installations: Canadian codes specify single air supply source.

 

Canadian customers and authorities having jurisdiction may use the sizing listed in

 

Table 2. When using a single air supply, the duct shall terminate within 1 foot (30

 

cm) above and within 2 feet (60 cm) horizontally from the burner level of the

 

appliance having the largest input.

 

 

 

*

 

 

 

 

 

 

 

Table 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Combined input of

Required

Acceptable equivalent

 

 

 

all appliances in

free area

 

duct diameter

 

 

 

confined space

of duct

 

A1

B2

 

 

 

BTU/hr(kW)

in2(cm2)

 

in(mm)

in(mm)

 

 

 

 

 

 

 

 

 

 

 

25,000(8)

7(45)

 

3(75)

4(100)

 

 

 

50,000(15)

7(45)

 

3(75)

4(100)

 

 

 

75,000(23)

11(70)

 

4(100)

5(125)

 

 

 

100,000(30)

14(90)

 

4(100)

5(125)

 

 

 

125,000(37)

18(120)

 

5(125)

6(150)

 

 

 

150,000(45)

22(140)

 

5(125)

6(150)

 

 

1. Maximum length of ducts in column A is 20 equivalent feet (6.1 meters).

 

2. Maximum length of ducts in column B is 50 equivalent feet (15.2 meters).

 

(c) EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR FROM

 

OUTDOORS.

 

 

 

 

 

 

For American installations: When supplying air directly from the outdoors using

 

horizontal ducting, each opening shall have a free minimum area of one square

 

inch per 2,000 BTU/hour (11 cm²/kW) of total input rating of all appliances in the

 

confined space.

 

 

 

 

 

 

For Canadian installations: Refer to Table 2 of part (b).

 

(d) EQUIPMENT LOCATED IN CONFINED SPACES; ALL AIR FROM

*U.S. installations require a dual duct system.

OUTDOORS THROUGH VENTILATED ATTIC.

For American installations: When supplying air directly through vertical ducting,

Figure 3: EQUIPMENT LOCATION AND

each opening shall have a free minimum area of one square inch per 4,000

COMBUSTION /VENTILATION AIR

BTU/hour (5.5 cm²/kW) of total input rating of all appliances in the confined space.

REQUIREMENTS

 

 

 

 

 

 

– 4 –

 

 

 

 

 

 

 

Page 4
Image 4
GSW Gas Fired Water Heater warranty Combustion Air Supply Ducts, Louvers and Grills, Air Opening Requirements