Haier AB124FAAHA Installation of Water Drainage Pipe, Pipe Tighten Amm Flare shape Size Torque

Models: AB124FAAHA AB484FCAHA AB244FCAHA AB184FCAHA AB094FAAHA AB424FCAHA

1 31
Download 31 pages 64 Kb
Page 22
Image 22
Large size seal pad 10 (accessory)
4mm below below500
Table 1

Installation Procedure

5. REFRIGERANT PIPING (As for outdoor piping, please refer to installation Manual of outdoor unit.)

Outdoor is precharged with refrigerant.

Be sure to see the Fig.1, when connecting and removing piping from unit.

For the size of the flare nut, please refer to Table 1.

Apply refrigerant oil at both inside and outside of lflare nut. Tighten it band tight 3-4 turns then tighten it. Use torque specified in Table 1. (Too much force may damage flare nut, causing gas leakage).

Check piping joints for gas leakage. Insulate piping as shown in Fig. below.

Cover joint of gas piping and insulator 7 with seal.

Apply refrigerant oil

Medium size seal pad 11 (accessory)

 

(Cover the piping joint

 

with seal pad.)

Torque spanner

Clamp 3

 

spanner

Insulator (accessory) 8

(For liquid pipe)

 

Piping joing

Insulator (accessory) 7

Gas pipe (For gas pipe)

Flare nut

Liquid pipe

Pipe

Tighten

A(mm)

 

Flare shape

size

torque

 

 

 

 

 

6.35

1420~1720N.cm

8.3~8.7

 

 

 

 

(144~176kgf.cm)

 

 

 

9.52

3270~3990N.cm

12.0~12.4

 

2

R0.4 ~ 0.8

 

(333~407kgf.cm)

 

 

6180~7540N.cm

 

0.5

45

 

 

 

 

 

15.88

18.6~19.0

90

A

 

(630~770kgf.cm)

 

19.05

9720~11860N.cm

22.9~23.3

 

 

 

(990~1210kgf.cm)

 

 

 

6. INSTALLATION OF WATER DRAINAGE PIPE

(1) Install water drainage pipe

Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethene; size: 25mm; O.D:32mm)

Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening.

If downward slope can't be made, take other measures to lift it up.

Keep a distance of 1-1.5m between suspending brackets, to make water hose straight.

1-1.5m

Slope over 1/100

Use the self-provided stiff pipe and clamp 1 with unit. Insert water pipe into water plug until it reaches the white tape. Tighten the clip until head of the screw is less than 4mm from hose.

Wind the drain hose to the clip using seal pad 9 .

Insulate drain hose in the room.

Tape (White)

Clamp

Clamp (accessory)

Self-provided stiff pipe

<Cautions for the drain water lifting pipe>

Installation height shall be less than 280mm.

There should be a right angle with unit, 300mm from unit.

 

300mm below 1~1.5m

Suspending bracket

Drain hose

 

below280220

below500

(accessory)

drain water lifting pipe

 

Clamp

(Note) (accessory)

Self-provided stiff pipe

(accessory) below75

The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it. If several water hoses join together, do as per following proceedures.

Over 100

Connect water hoses with a T joint.

Specifications of the water hoses shall meet the requirements for the unit running.

20

Page 22
Image 22
Haier AB124FAAHA, AB424FCAHA, AB244FCAHA Installation of Water Drainage Pipe, Pipe Tighten Amm Flare shape Size Torque