Haier AB484FCAHA, AB424FCAHA, AB244FCAHA Error display Indoor unit malfunction display code

Models: AB124FAAHA AB484FCAHA AB244FCAHA AB184FCAHA AB094FAAHA AB424FCAHA

1 31
Download 31 pages 64 Kb
Page 15
Image 15

When Trouble Happens

1. Error display

Indoor unit malfunction display code

Indoor unit malfunction

Display code

Indoor unit malfunction

Display code

 

 

 

 

Float switch or water motor abnormal

E0

The communication with electronic

E7

Outdoor unit abnormal

E1

expansion box is abnormal

 

Liquid temperature sensor is abnormal

E3

The communication between the

E8

 

wire remote controller and indoor

 

 

 

 

Gas temperature sensor is abnormal

E4

unit control board is abnormal

 

 

 

 

 

Indoor unit adress abnormal

E5

The communication between indoor

E9

(Firstly you saw E5 in controller LCD,

 

and outdoor unit is abnormal

 

and then the failure code is changed

 

 

 

 

 

from E5 to E9)

 

Water temp. sensor is abnormal (Only

E0

 

 

used for the twin energy source function)

Indoor unit EEPROM data is abnormal

E6

 

 

 

 

 

Remote controller Timer and Operation indicator malfunction code When the unit running, Timer indicator flash stand for indoor unit malfunction

Timer indicator

Indoor unit malfunction

Flashing times

 

 

 

Flashing once

The liquid tube temperature sensor is abnormal

 

 

Flashing twice

The gas tube temperature sensor is abnormal

 

 

Flashing 3 times

The environment temperature sensor is abnormal

 

 

Flashing 4 times

The communication with outdoor unit is abnormal

 

 

Flashing 5 times

The ommunication with the electronic expansion valve control board is abnormal

 

 

Flashing 10 times

Indoor unit PG fan motor is abnormal

 

 

Flashing 11 times

Indoor unit water overflow or float switch is abnormal

 

 

Flashing 12 times

Indoor unit EEPROM data is abnormal

 

 

Flashing 15 times

Water temp. sensor is abnormal£¤Only used for the twin energy source function£'

 

 

Outdoor unit malfunction display code

When the wire remote controller display E1,Can check the outdoor unit control board LED1 or outdoor unit malfunction display code to sure outdoor unit malfunction.

When the operation indicator flashing stand for outdoor unit malfunction,Operation indicator flashing times can't determinant outdoor unit malfunction ,You must check the outdoor unit control board LED1 flashing times or outdoor unit malfunction display code to sure outdoor unit malfunction.

Others malfunction manual plese read the outdoor unit manual.