Installation Procedures

Mounting Air Inlet Grid and Angle Covers

(1) Mounting the air inlet grid:

Take care not to wind the lead of the wind deflector motor during mounting the air inlet grid.

(2)For Model AB184-484FCAHA units, the angle covers should be mounted on the angles.

¢Tie the thread of the angle cover onto the cleat on the decorated board as shown in Fig. 6.

¢Mount the angle cover onto the decorated board (as shown in Fig. 7).

cleat

Slide the 5 locks to mount angle covers to fit the holes on decorated board

Fig.6

Fig.7

£¡ Attention

For proper drainage, the drainpipes should be connected according to the installation manual. Heat preservation should be performed as to prevent condensing. Improper connections may cause the water leakage.

Requirements:

The drainpipe of the indoor unit should be heat-insulated.

Heat insulation should be treated for the connection with the indoor unit. Improper heat insulation may cause condensing.

The drainpipe with the down gradient of over 1/100 can’t be in the S shape, or abnormal sound can be caused. The lateral length of the drainpipe should be kept with 20m. Under the condition of long pipes, supports can

be provided every 1.52m as to avoid unevenness.

The central piping should be connected according the following drawing.

Take care not to apply external force on the connection of the drainpipes.

1.5m~2m support bracket

 

as big as possible (about 10 CM)

 

 

heat down gradient

s-shape elbow

down gradient

VP30

insulating over 1/100

 

 

over 1/100

 

material

 

 

 

 

 

23

Page 25
Image 25
Haier AB244FCAHA Cleat, 5m~2m support bracket, Heat down gradient Shape elbow, Insulating over 1/100 Over 1/100 Material