Installation Manual For Indoor Unit
5. Electric wiring
WARNING
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS. GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
(1)Selection of size of power supply and interconnecting wires. Precautions for Electric wiring
Electric wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated grip on the ends of the wires.
Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.)
Item
Model
Circuit | breaker | Power source | Earth leakage breaker | |
Phase Switch breaker | Overcurrent protector | wire size | Switch | Leak |
(minimum) | ||||
(A) | rated capacity (A) | (mm2) | breaker(A) | current(mA) |
For series 182 | 1 | 40 | 26 | 2.5 | 40 | 30 | |
For series 242 | 1 | 40 | 26 | 4.0 | 40 | 30 | |
For series 282 362 | 1 | 40 | 26 | 6.0 | 40 | 30 | |
For series | 3 | 30 | 20 | 2.5 | 30 | 30 | |
282 362 482 | |||||||
|
|
|
|
|
|
(2) Wiring connection
Make wiring to supply power to the indoor unit, so that the power for the outdoor unit is supplied by terminals.
For series 182
INDOOR UNIT TERMINAL BLOCK
OUTDOOR UNIT TERMINAL BLOCK
1 2 3 N L | Y/G |
|
1 | 2 | 3 |
|
| Y/G |
Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by terminals.
For series 242 282 362 | For series 282 362 482 |
| INDOOR UNIT | 1 | 2 | 3 | Y/G |
| INDOOR UNIT | 1 2 3 |
| TERMINAL BLOCK |
|
|
|
| TERMINAL BLOCK | ||
|
|
|
|
|
| OUTDOOR UNIT | Y/G | N 1 2 3 |
OUTDOOR UNIT | L N | 1 | 2 | 3 |
| R S T | ||
| TERMINAL BLOCK | |||||||
TERMINAL BLOCK |
|
|
| Y/G |
|
|
| |
|
|
|
|
|
|
|
|
POWER SUPPLY:
POWER SUPPLY: 1PH,
Y/G
Y/G
18