Installation Procedure | Electric wiring | |
|
|
|
(1)Before starting test run (for all Heat pump models)
Confirm whether the power source breaker (main switch) of the unit has been turned on for over 12 hrs to energize the crankcase heater in advance of operation.
(2)Test run
Run the unit continuously for about 30 minutes, and check the following. Suction pressure at check joint of service valve for gas pipe.
Discharge pressure at check joint on the compressor discharge pipe. Temperature difference between return air and supply air for indoor unit.
10. Trouble display
Trouble description | Display of LED borad | Analyze and diagnose | ||
| LED |
|
| |
|
|
|
| |
Spdu module failure | 00001 | Spdu module failure | ||
|
|
|
| |
Abnormal of DC moter | 00010 | Jam of DC motor or motor failure | ||
|
|
|
| |
Communication error between indoor and outdoor | 00011 | Communication fail over 4min | ||
unit |
|
|
| |
Compressor discharging temprerture protection | 00100 | Compressor discharging tempreature |
| |
|
| over 120 centigrade |
| |
Spdu module over current protection | 00101 | Current of spdu module over 21A last | ||
|
| 4set | ||
Abnormal of outdoor ambietn sensor | 00110 | Outdoor ambietn sensor |
| |
|
|
| ||
Abnormal of piping sensor or suction sensor | 00111 | Piping sensor or suction sensor short- | ||
|
| circuit or |
| |
High pressure protection | 01000 | System high pressure over 4.5Mpa | ||
|
|
| ||
Abnormal of compressor discharge sensor | 01001 | Compressor discharge sensor short- |
| |
|
| circuit or |
| |
The power supply is not the 50Hz | 01010 | The power supply is not the 50Hz | ||
|
|
| ||
Eeprom failure | 01110 | Outdoor main board eeprom fail |
| |
Compressor JAM | 01111 | Inner compressor is abnormal | ||
Compressor vibration abnormal | 10000 | Compressor vibration abnormal when |
| |
| ||||
|
| |||
Compressor | 10001 | Compressor |
| |
Rotor of inner compressor is malposition | 10010 | Rotor of inner compressor is malposition | ||
|
| when |
| |
10011 | ||||
|
| module |
| |
Compressor failure | 10100 | Compressor failure | ||
Compressor suction sensor over high | 10101 | In operation the suction temperature |
| |
|
| over 40 centigrade | ||
Communication error between main board and | 10110 | Communication error between main |
| |
spdu module |
| board and spdu module |
| |
Spdu module temperture protection | 10111 | Spdu module temperture is too high |
| |
Low pressure protection | 11000 | System low pressure under 0.15Mpa | ||
|
|
|
|
Note:
For display of LED board, the number "1" mean the LED is light. the number "0" mean the LED is OFF.
User should not to change the dip switch of LED board.
Please consult the operation and instrucion to get detailed information about outdoor unit trouble.