7. Charging amount of refrigerant

Installation Procedure

Refrigerant piping

6. Piping method: to use wacuum pump( e.g. AU182AFERA)

1 .Detach the service portis cap of 3-way valve, the valve rod's cap for 2-way valve and 3-way valves, connect the service port into the projection of charge hose (low) for gaugemanifold. Then connect the projection of charge hose (center) for gaugemanifold into vacuum pump.

2 .Open the handle at low in gaugemanifold, operate vacuum pump. If the scale-moves of gause (low) reach vacuum condition in a moment, check 1 again.

3 .Vacuumize for over 15min. And check the level gauge which should read -0.1MPa (-76 cm Hg) at low pressure side. After the completion of vacuumizing, close the handle 'Lo' in the vacuum pump. Check the condition of the scale and hold it for 1-2min. If the scale-moves back in spite of tightening, make flaring work again, then return to the beginning of 3 .

4 .Open the valve rod for the 2-way valve to and an angle of anticlockwise 90 degree. After 6 seconds, close the 2- way valve and make the inspection of gas leakge.

5 .No gas leakage?

In case of gas leakage, tighten

 

parts of pipe connection. If

 

leakage stops, then proceed 6

 

steps.

6 .Detach the charge hose from the service port, open 2- way valve and 3-way. Turn the valve rod anticlockwise until hitting lightly.

7 .To prevent the gas leakage, turn the service ports cap,

Liquid stop valve

 

Gas stop valve

2 way valve

 

3 way valve

Gauge maifold(R410A)

 

 

Vacuum pump(R410A)

Open

Close

2 way valve Manual backgroundManual background

Manual backgroundManual background 3 way valve 900 Manual backgroundManual backgroundManual background

Service port

Manual background 900 for 6 sec.

If it does not stop gas leakage, discharge whole refrigerants from the service port. After flaring work again and vacuumize, fill up prescribed refrigerant from the gas cylinder.

2 way valve

 

2 way valve

 

 

 

6

3 way valve

3 way valve

 

6

Valve rod cap

 

Valve rod cap

 

 

 

 

Service port cap

the valve rodis cap for 2-way valve and 3-way's a little more than the point where the torque increases suddenly.

CAUTION:If the refrigerant of the air conditioner leaks, it is necessary to make all the refrigerant out. Vacuumize first, then charge the liquid refrigerant into air conditioner according to the amount marked on the name plate.

7. Charging amount of refrigerant

When the total length (L) of the two indoor units' connecting pipe is less than 5m, it is unnecessary to charge additional refrigerant.

If the connecting pipe (L) exceeds 5m, it shall charge Mg additional refrigerant per meter. That is: Refrigerant charging amount = (L-5) x M (g)

For AU122AEERA, AU182AFERA, M=30

For AU242AGERA, AU282AHERA,AU362AHERA, AU36NAHERA,AU422AIERA, AU42NAIERA.AU522AIERA,AU52NAIERA,M=50

Manual background Only in COOLING operation can charge the additional refrigerant.

Manual background When charging, the refrigerant shall be charged from the charging nozzle of low pressure vavle. Manual background Be carefull when charging refrigerant, do not let the air mix into the system,and must charge the additional refrigerant in liquid condition.